| 2007-07-25 14:40:16 | *****DENIED***** |
| | |
| | |
| | 1.ON SHEET A1 UNDER APPLICABLE CODES, INCLUDE 2003 |
| | NFPA 101- LIFE SAFETY CODE AND RECTIFY 2004 (IN LIEU |
| | OF) 2000 FLORIDA FIRE PREVENTION CODE. |
| | |
| | 2.THE COMPLETE ADDRESS, INCLUDING THE SUITE NUMBER, |
| | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| | SHEET. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER ACCESS TO OR EGRESS FROM THE SAID |
| | PROPERTY OR THE VICINITY THEREOF (INCLUDING EXITS, EXIT |
| | AISLE CORRIDORS. |
| | |
| | 5.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE |
| | FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 6.ON SHEET A4, THERE IS AN EXIT LIGHT IN FRONT OF A |
| | DOOR THAT ACCESS CAN BE MADE TO THE EXISTING STAIRS, |
| | HOWEVER THE EXIT LIGHT DIRECTS PERSON(S) AWAY FROM THIS |
| | DOOR.CAN THAT EXISTING STAIR BE USED AS A MEANS OF |
| | EGRESS? |
| | |
| | 7.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLERS? |
| | IF SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR |
| | THE SPRINKLER REMODEL. |
| | |
| | 8.WILL THE SCOPE OF WORK IMPACT THE FIRE ALARM |
| | DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED FOR THE FIRE ALARM REMODEL. |
| | |
| | 9.SHOW THE LOCATION OF THE 2A:10BC FIRE |
| | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL |
| | DISTANCE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |