Plan Review Notes
Plan Review Notes For Permit 07060046
Permit Number 07060046
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-21 19:50:53*** UNSAT ***
  
 BAR LOUIE
  
 1) NOTE: PLEASE SEE THE PLANS WERE ONLY SUBMITTED FOR
 *PLAN REVIEW* AND HAVE NOT BEEN SUBMITTED FOR PERMIT.
 PLEASE KNOW EVEN WHEN PLANS ARE CODE COMPLIANT AND
 PERMIT APPLICATION HAS NOT BEEN MADE, THE STATUS WILL
 STILL BE IN A FAILED STATUS UNTIL PERMIT IS MADE. THERE
 ARE SEVERAL ITEMS WHICH ARE REVIEWED AFTER PERMIT
 APPLICATION IS MADE. VALUE, LICENSING ETC.
 PLEASE SEE THAT PLANS WHEN SUBMITTED FOR PERMIT MUST
 CONTAIN THE *CITY PLACE * STAMP AND SIGNATURE OF
 LANDLORD APPROVAL.
  
 2) NOTE:PLEASE SEE THE SUBMITTED DOCUMENTS REQUIRE
 THE CODES TO BE STATED ON PLANS.
 PLEASE SEE THE FOLLOWING ARE REQUIRED FOR ELECTRICAL
 AND OTHERS WILL BE REQUIRED FOR OTHER TRADES. PLEASE
 KNOW AS OF DECEMBER 8TH, 2006 THE STATE ADOPTED THE
 2006 REVISIONS TO THE 2004 FBC AND THE 2005 NFPA-70.
 PLEASE LIST THE FOLLOWING
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE CODES ARE REFLECTED ON PLANS WHICH ARE
 NOT CODES IN THE STATE OF FLORIDA (2003 FBC?)
 ** PLEASE SEE COMMENTS FROM OTHER TRADES FOR ANY OTHER
 CODES WHICH MAY BE NEEDED.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED PER FAC 61G1-16.004 AND FLORIDA STATUTES
 481.219.
 PLEASE SEE THAT DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION DOES NOT CONTAIN ANY LICENSE INFORMATION FOR
 THE FIRM.
 PLEASE SEE MISSING THE PRINTED NAME, PRINTED LICENSE
 NUMBER AND FIRM LICENSE NUMBER.
 PLEASE SEE THE DATE MUST ALSO BE PLACED ON PLANS WHEN
 SIGNING AND SEALING PLANS PER FS 481.221.
  
 4) NOTE: PLEASE SUBMIT ELECTRICAL PLANS FOR FBC CHAPTER
 13 COMPLIANCE. PLEASE SEE THE NEW LIGHTING IS REQUIRED
 TO LIGHTING CONTROLS PER 13-101, 13-415.1.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SEE ONLY THE NEW BEING INSTALLED IS REQUIRED.
 PLEASE PROVIDE METHOD OF SYSTEM OR DEVICES BEING
 INSTALLED.
 PLEASE PROVIDE TIME SCHEDULING IF INSTALLING A SYSTEM.
 PLEASE PROVIDE TIME ON OCCUPANCY SENSORS IF USED AS
 CONTROLS OR OVER RIDES. (30 MINS MAX)
 PLEASE PROVIDE TIME FOR TIMER TYPE CONTROLS IF USED.(4
 HRS MAX).
 PLEASE PROVIDE LOCATIONS OF ALL DEVICES.
  
 ** PLEASE KNOW AS NO INFORMATION WAS SUBMITTED FOR
 REVIEW THERE MAY BE NEW COMMENTS ON NEXT SUBMITTAL.
  
 5) NOTE: PLEASE INDICATE AND SHOW ALL ELECTRICAL
 CIRCUITING ON PLANS FOR NEW LIGHTING ETC. PLEASE SEE
 700.12FFOR CIRCUITING OF EMERGENCY AND EXIT LIGHTS.
 PLEASE SUBMIT THE ABOVE ALONG WITH PANEL SCHEDULE(S)
 FOR CIRCUITING.
 PLEASE INCLUDE LOAD CALCULATIONS FOR NEW LOADS TO
 EXISTING PANELS.
 240.4, 408.4, 310.16, 220.12, 220.14, 220.42, 220.44,
 ETC.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE INDICATE THE MINIMUM REQUIRED FA
 DEVICES FOR HORNS, STROBES OR HORN/STROBES. PLEASE KNOW
 IF AS STATED ON SHEETS AND EVEN AS THE FIRE ALARM AND
 FIRE SPRINKLER WORK IS UNDER SEPARATE PERMITS THE BASE
 BUILD OUT PLANS IS REQUIRED UNDER FLORIDA STATUTES AND
 FBC TO SHOW BASE REQUIRED CODE DESIGNS AND INTENT.
 PLEASE PROVIDE LOCATIONS AND MINIMUM ADA LEVELS PER FBC
 11-4.28.1, .2 AND .3(4).
 PLEASE SEE FS 633, FBC 106.3.5.1.2.
  
 7) NOTE: PLEASE SEE PLAN REVIEW APPLICATION AND SITE
 PLAN ON PLANS INDICATES 700 S ROSEMARY. PLEASE VERIFY
 ADDRESS OF THE LOCATION WHICH THE NEW REMODEL IS TAKING
 PLACE. PLEASE SEE THAT THE CITY PLACE OFFICE LOCATION
 IS THAT OF 700 S ROSEMARY AND THE LOCATION WHICH THE
 REMODEL IS TAKING PLACE.
  
 ** PLEASE KNOW AS STATED ABOVE, THERE ARE SEVERAL ITEMS
 NOT SUBMITTED FOR REVIEW FOR CODE COMPLIANCE AND A
 COMPLETE REVIEW CAN NOT BE DONE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved