| 2007-06-27 11:19:51 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT |
| | APPLICATION REQUIREMENTS ATTACHED TO THE GAS COMMENTS |
| | FOR FUTURE PERMITS: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| | DOES NOT INDICATE CORRESPONDING LENGTHS TO CUT |
| | SECTIONS. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE SUBMITTED DRAWING DOES NOT INDICATE THE ABOVE |
| | GROUND PIPING MATERIAL. PLEASE INDICATE THIS ON THE |
| | RESUBMITTAL. PIPING AND SHUT OFF VALVES MUST BE FULL |
| | SIZE 1-1/2" TO PROPOSED POOL HEATER. PIPING CAN BE |
| | REDUCED AT THE POOL HEATER CONNECTION. PLEASE INDICATE |
| | THIS ON THE RESUBMITTED ISOMETRIC. |
| | |
| | 3. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE TOTAL LENGTH INDICATED AS 110', IS THIS THE |
| | LONGEST LENGTH OF THE SYSTEM INCLUDING THE EXISTING GAS |
| | TO THE HOUSE APPLIANCES. PLEASE CLARIFY THIS ON THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |