| Notes |
| Date |
Text |
| 2008-06-10 09:55:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) COOLING LOAD CALCULATIONS ARE REQUIRING 21,025 TOTAL | | | COOLING BTU'S, THE MECHANICAL PLANS ARE SHOWING 30,000 | | | TOTAL COOLING BTU'S. THE PLANS CAN ONLY CALL FOR 15% | | | MORE TOTAL COOLING BTU'S THAN THE COOLING LOAD | | | CALCULATIONS, PER 2004 FBC 13-6071..ABC.1.1.A 2.5 TON | | | A/C SYSTEM IS TO LARGE FOR THE ADDITION, PER THE | | | COOLING LOAD CALCULATIONS, PLEASE CORRECT. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-103.3. | | | | | | 3) AS NOTED IN LAST REVIEW 11-13-07 NOTE #3. THE | | | MECHANICAL PLANS ALSO NEED THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON | | | THEM, SEE W.P.B. AMEND. 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|