Plan Review Notes
Plan Review Notes For Permit 07060013
Permit Number 07060013
Review Stop M
Sequence Number 3
Notes
Date Text
2008-06-10 09:55:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS ARE REQUIRING 21,025 TOTAL
 COOLING BTU'S, THE MECHANICAL PLANS ARE SHOWING 30,000
 TOTAL COOLING BTU'S. THE PLANS CAN ONLY CALL FOR 15%
 MORE TOTAL COOLING BTU'S THAN THE COOLING LOAD
 CALCULATIONS, PER 2004 FBC 13-6071..ABC.1.1.A 2.5 TON
 A/C SYSTEM IS TO LARGE FOR THE ADDITION, PER THE
 COOLING LOAD CALCULATIONS, PLEASE CORRECT.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-103.3.
  
 3) AS NOTED IN LAST REVIEW 11-13-07 NOTE #3. THE
 MECHANICAL PLANS ALSO NEED THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN, ON
 THEM, SEE W.P.B. AMEND. 106.1.3.
  