| 2007-11-13 15:50:14 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) THE A/C SYSTEM LISTED COULD NOT BE FOUND IN THE ARI | | | DIRECTORY, PLEASE SUBMIT THE ARI LISTING FOR THE | | | SYSTEM. SEE 2004 FBC 13-607.1.ABC.3.1.1. | | | | | | 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J. | | | CAL'S.), SEE 2004 FBC 13-607.1.ABC.1. | | | | | | 3) THE MECHANICAL PLANS NEED THE PRINTED NAME AND | | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN ON | | | THEM, SEE W.P.B. AMEND. 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|