| Plan Review Notes For Permit 07060007 |
| Permit Number |
07060007 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-12 13:24:33 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.)CONNECTION TYPES A AND B ARE FOR POURED CONCRETE | | | SUBSTRATES.REVISE THE INSTALLATION SCHEDULE. | | | | | | 2.)3" EDGE DISTANCE REQUIRES A FACTOR OF .86 FOR | | | ANCHOR SPACING, SEE PRODUCT APPROVAL SHEET 14. | | | |
|