Plan Review Notes
Plan Review Notes For Permit 07051187
Permit Number 07051187
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-09 19:02:41PROJECT: 851 VILLAGE BLVD. #502
  
 PROJECT DETAIL: INTERIOR DEMOLITION
  
 REVIEW: 2004 FLORIDA EXISTING BUILDING CODE WITH 2006
 REVISIONS
  
 STATUS: DENIED
  
  
  
 COMMENTS:
  
 1)PLEASE CONTACT MR. ALEX ORTEGA OF THE DEP AT
 355.3023,EXT. 1148 PRIOR TO COMMENCING DEMOLITION. AN
 APPROVAL FROM THIS AGENCY MUST BE OBTAINED AS PER THE
 FOLLOWING CODE SECTION:
  
 105.9 ASBESTOS.
 THE ENFORCING AGENCY SHALL REQUIRE EACH BUILDING PERMIT
 FOR THE DEMOLITION OR RENOVATION OF AN EXISTING
 STRUCTURE TO CONTAIN AN ASBESTOS NOTIFICATION STATEMENT
 WHICH INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR HER INTENTIONS TO
 REMOVE ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH
 STATE AND FEDERAL LAW.
  
 2) REQUIRE SIGNED AND SEALED PLANS AS PER THE FOLLOWING
 REQUIREMENTS:
  
 A PROFESSIONAL ENGINEER SHALL SIGN HIS
 NAME AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS,
 REPORTS AND FINAL BID
 DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER'S REPRESENTATIVE, OR OTHER DOCU-
 MENTS PREPARED OR ISSUED BY SAID REGIS-
 TRANT AND BEING FILED FOR PUBLIC RECORD.
 THE DATE THAT THE SIGNATURE AND SEAL IS
 AFFIXED AS PROVIDED HEREIN SHALL BE EN-
 TERED ON SAID PLANS, SPECIFICATIONS, RE-
 PORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1)
 FS 471.025
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER THE PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. FAC 61G15-23.002(2)
 FS 471.025
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  
 3) THE PROPOSED SCOPE OF WORK IF FOR DEMOLITION ONLY. A
 DEMOLITION AND REMODEL PLAN HAS BEEN SUBMITTED ON SHEET
 A1.0. PLEASE REVISE SCOPE OF WORK OR PROVIDE A FLOOR
 PLAN FOR DEMOLITION ONLY. IF THE INTENDED SCOPE OF WORK
 IS REVISED A COMPLETE SET OF PLANS MUST BE SUBMITTED.
  
 4) A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 5) IF THERE ARE ANY QUESTIONS WITH REFERENCE TO THESE
 COMMENTS, PLEASE CONTACT ME PRIOR TO RE-SUBMITTING THE
 APPLICABLE PLANS.
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]