| 2007-09-27 16:14:21 | | | | | | | DENIED | | | | | | 1)DESIGN CRITERIA ON S/3 AND STRUCTURAL CALCULATIONS | | | FOR THE NANA DOOR SYSTEM DO NOT MATCH, CALC'S CANNOT BE | | | LESS THAN WHAT THE DRAWINGS SPECIFY | | | | | | 2)IF 140 MPH EXP "B" WHICH IS THE CORRECT DESIGNATION | | | FOR THE CITY OF WEST PALM BEACH IS USED AS THE WIND | | | DESIGN CRITERIA ALL PRODUCT APPROVALS WILL WORK | | | | | | 3)PLEASE CORRECT PAGES A/3.0 AND A/3.1 MANY WINDOW | | | MARKS AND MEASUREMENTS DO NOT MATCH WINDOW SCHEDULE | | | | | | 4)PER 713.13(2) F.S. | | | IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT | | | COMMENCED WITHIN 90 DAYS OF RECORDING, THE NOTICE IS | | | VOID | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|