| Plan Review Notes For Permit 07051183 |
| Permit Number |
07051183 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-09-15 09:30:28 | | | | | | | DENIED | | | | | | 1)THE DESIGN PRESSURE ON THE DRAWING EXCEED THE | | | MAXIMUM ALLOWABLE PRESSURES IN THE PRODUCT APPROVALS | | | FOR THE NANA FOLDING DOORS (-55 PSF), THE FRENCH DOORS | | | DEPENDING UPON GLASS TYPE (TYPE B -76 PSF), HORIZONTAL | | | SLIDERS (-80 PSF), AND FIXED WINDOWS (-78 PSF). | | | *****THESE COMMENTS WERE ADDRESSED ON 2ND REVIEWUNDER | | | NEW COMMENTS 1, 2, AND 3.***** | | | | | | *****NOTE AS A SUGGESTION, THE CITY OF WEST PALM BEACH | | | IN GENERAL AND IN THIS CASE IS IN A 140 MPH EXPOSURE | | | "B" WIND ZONE, UNDER THESE PARAMETERS THE PRODUCT | | | APPROVALS WOULD MEET DESIGN PRESSURE REQUIREMENTS***** | | | | | | 2)UNDER LEVEL 2 ALTERATIONS THE MAIN FLOOR BATHROOM | | | IS REQUIRED TO MEET THE ACCESSIBILITY REQUIREMENTS OF | | | THE FBC 2004, AS SUCH PROVIDE AT MINIMUM 1 ACCESSIBLE | | | BATHROOM PER R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 | | | DEGREES | | | | | | 3)PLEASE REMOVE ALL OLD SHEETS FROM RESUBMITTED | | | PERMIT APPLICATION | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|