Date Text
2007-08-09 09:48:55DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. SHEET P-1.0 SANITARY PIPING ISOMETRIC:
 A} **OK**
 B} **OK**
 C} **NO/OK**PER FBC-2004 PLUMBING SECTION 708.9
 ACCESS, PLEASE INDICATE THE CLEANOUT FOR THE WASHING
 MACHINE AT 4' AFF.
 ** THE CORRECTED WASHING MACHINE ISOMETRIC IS WRONG THE
 DRAIN STACK SHALL BE 3"AND THE FIXTURE DRAIN SHALL BE
 2" PER FBC-2004 PLUMBING SECTION 406.3 AND THE CLEANOUT
 SHALL BE 3" PER FBC-2004 PLUMBING SECTION 708.7 AND BE
 LOCATED AT 4' AFF PER FBC-2004 PLUMBING SECTION 708.9
 AND THE CLEANOUT SHALL BE LOCATED ABOVE THE FIXTURE
 DRAIN.
 D} **OK**
  
 THE FOLLOWING ARE NEW ITEMS:
  
 3. SHEET A-2.1 2ND FLOOR DEMOLITION PLAN: THE EXISTING
 BATH TUB SHOULD BE #17 NOT #19 PER THE DEMOLITION KEY
 NOTES.
  
 4. SHEET P-1.O SANITARY PIPING ISOMETRIC: PLEASE
 CORRECT THE WORDING FOR THE NOTE ON SLOPE TO THE
 FOLLOWING PER TABLE 704.1. "SLOPE ALL PIPING 2-1/2" AND
 LESS @ 1/4" PER FT. AND SLOPE ALL PIPING 3" TO 6" @
 1/8" PER FT.".
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  