Plan Review Notes
Plan Review Notes For Permit 07051183
Permit Number 07051183
Review Stop G
Sequence Number 2
Notes
Date Text
2007-08-09 10:52:01DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **OK**
  
 2. **NO**SHEET P-2.0 THE RESUBMITTED GAS ISOMETRIC
 INDICATING THE SLEEVE IS NOT COMPLIANT PER FBC-2004
 FUEL GAS , SECTION 404.11 PIPING UNDERGROUND BENEATH
 BUILDINGS IS PROHIBITED EXCEPT WHERE THE PIPING IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC PIPE OR
 STEEL PIPE DESIGNED TO WITHSTAND THE SUPERIMPOSED
 LOADS. SUCH CONDUIT SHALL EXTEND INTO AN OCCUPIABLE
 PORTION OF THE BUILDING AND, AT THE POINT WHERE THE
 CONDUIT TERMINATES IN THE BUILDING, THE SPACE BETWEEN
 THE CONDUIT AND THE GAS PIPING SHALL BE SEALED TO
 PREVENT THE POSSIBLE ENTRANCE OF ANY GAS LEAKAGE.WHERE
 THE END SEALING IS CAPABLE OF WITHSTANDING THE FULL
 PRESSURE OF THE GAS PIPE, THE CONDUIT SHALL BE DESIGNED
 FOR THE SAME PRESSURE AS THE PIPE. SUCH CONDUIT SHALL
 EXTEND NOT LESS THAN 4 INCHES (102 MM) OUTSIDE THE
 BUILDING, SHALL BE VENTED ABOVE GRADE TO THE OUTDOORS,
 AND SHALL BE INSTALLED SO AS TO PREVENT THE ENTRANCE OF
 WATER AND INSECTS. THE CONDUIT SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 404.8.
 **PLEASE REFERENCE THE DETAIL ATTACHED TO THE GAS
 COMMENTS AND PLEASE HAVE SHEETS P-1.0 NOTE #4 AND SHEET
 P-2.0 GAS ISOMETRIC REFLECT THIS DETAIL ON THE
 RESUBMITTAL.
  
 3. **NO** SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE CORRESPONDING LENGTHS ARE NOT BEING INDICATED
 FOR ALL CUT SECTIONS OF PIPE ON SHEET P-2.0 GAS
 ISOMETRIC.
  
 4. **NO** SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS CAN NOT BE VERIFIED UNTIL GAS COMMENT #3 HAS
 BEEN ADDRESSED.
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 5. SHEET P-2.0 GAS ISOMETRIC: THE FBC GAS SIZING TABLE
 402.4(1) IS WRONG, THE CORRECT SIZING TABLE IS 402.4(2)
 PLEASE CORRECT THIS ON THE RESUB.
  
 6. PLEASE ADD THE FOLLOWING TO THE GAS NOTES ON SHEET
 P-2.0:
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION. METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE, SHALL BE
 PROTECTED IN AN APPROVED MATTER.
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPINGS SHALL BE APPROVED FOR THE
 APPLICATION AND SHALL BE FACTORY APPLIED.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]