Plan Review Notes
Plan Review Notes For Permit 07051183
Permit Number 07051183
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-02 17:25:38 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} SHEET E-2.0, PROVIDE CONDUCTOR AND CONDUIT SIZE AND
 TYPE FOR THE SERVICE RISER ON THE RISER DIAGRAM. ALSO
 THE WORD "EXISTING" STILL APPEARS FOR THAT RISER.
  
 2} SHEET E-2.0, PANEL "B" ON THE RISER IS MCB, ON THE
 SCHEDULE IT'S MLO. CLARIFY.
  
 3} SHEET E-2.0, THE FEEDER FOR PANEL "A" IS 1/0 ON THE
 RISER, LISTED AS 2/0 IN PANEL "B" SCHEDULE. NOTE 1/0 IS
 SUFFICIENT.
  
 4} SHEET E-1.0 THE DOORWAY BETWEEN THE OFFICE AND
 KITCHEN BEING CLOSED OFF REQUIRES A RECEPTACLE TO BE
 ADDED FOR COUNTERTOP SPACING, 210.52(C)(1).
  
 5} THE COUNTER NEXT TO THE RELOCATED REFRIGERATOR
 (KITCHEN) REQUIRES A RECEPTACLE, 210.51(C)(1).
  
 6} A RECEPTACLE IS REQUIRED AT BOTH SIDES OF THE RANGE
 IN THE ISLAND PER 210.52(C)(2).
  
 7} ALL COUNTERTOP RECEPTACLES IN THE KITCHEN MUST BE
 GFCI PROTECTED, 210.8(A)(6).
  
 8} THE JUCUZZI MUST BE GFCI PROTECTED PER
 680.43(A)(3).
  
 THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE LEVEL
 OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THE EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE
 PLAN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE
 BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE
 CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE
 ARTICLE. MAKE A NOTE ON THE PLAN FOR FIELD
 CLARIFICATION
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718