| 2007-08-02 17:25:38 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} SHEET E-2.0, PROVIDE CONDUCTOR AND CONDUIT SIZE AND |
| | TYPE FOR THE SERVICE RISER ON THE RISER DIAGRAM. ALSO |
| | THE WORD "EXISTING" STILL APPEARS FOR THAT RISER. |
| | |
| | 2} SHEET E-2.0, PANEL "B" ON THE RISER IS MCB, ON THE |
| | SCHEDULE IT'S MLO. CLARIFY. |
| | |
| | 3} SHEET E-2.0, THE FEEDER FOR PANEL "A" IS 1/0 ON THE |
| | RISER, LISTED AS 2/0 IN PANEL "B" SCHEDULE. NOTE 1/0 IS |
| | SUFFICIENT. |
| | |
| | 4} SHEET E-1.0 THE DOORWAY BETWEEN THE OFFICE AND |
| | KITCHEN BEING CLOSED OFF REQUIRES A RECEPTACLE TO BE |
| | ADDED FOR COUNTERTOP SPACING, 210.52(C)(1). |
| | |
| | 5} THE COUNTER NEXT TO THE RELOCATED REFRIGERATOR |
| | (KITCHEN) REQUIRES A RECEPTACLE, 210.51(C)(1). |
| | |
| | 6} A RECEPTACLE IS REQUIRED AT BOTH SIDES OF THE RANGE |
| | IN THE ISLAND PER 210.52(C)(2). |
| | |
| | 7} ALL COUNTERTOP RECEPTACLES IN THE KITCHEN MUST BE |
| | GFCI PROTECTED, 210.8(A)(6). |
| | |
| | 8} THE JUCUZZI MUST BE GFCI PROTECTED PER |
| | 680.43(A)(3). |
| | |
| | THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE LEVEL |
| | OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF |
| | THE EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE SEE |
| | ARTICLE. MAKE A NOTE ON THE PLAN FOR FIELD |
| | CLARIFICATION |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |