| 2007-08-13 18:22:57 | |
| | |
| | DENIED 2ND REVIEW |
| | |
| | THE FOLLOWING REVIEW COMMENTS WERE NOT FULLY ADDRESSED |
| | ON THE FIRST REVIEW |
| | |
| | 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES, |
| | AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/ |
| | FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN |
| | ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS |
| | PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | ******NOTE PRODUCT APPROVALS WERE NOT SUBMITTED FOR THE |
| | MULLIONS THAT ARE REQUIRED AT THE GREAT ROOM FRONT |
| | WINDOWS OR THE FRONT ENTRY DOOR****** |
| | |
| | 3)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE. |
| | THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG. |
| | WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE |
| | DENIED |
| | |
| | ****** NOTE: THESE PRODUCT APPROVALS CAN BE FOUND AT |
| | THE ABOVE WEB SITE, THE FL#'SARE WRITTEN AT THE TOP |
| | OF THE MIAMI-DADE REPORTS. PLEASE SEE THAT THE |
| | MIAMI-DADE NOA'S ARE IN THE CERTIFYING AGENCY FOR THE |
| | STATE APPROVALS AND WILL ALSO NEED TO BE SUBMITTED WITH |
| | THE STATE COVER SHEETS****** |
| | |
| | 4)MANY KEY NOTES ON ARCHITECTURAL SHEETS DO NOT |
| | CORRESPOND WITH DRAWINGS PLEASE CLARIFY |
| | |
| | ******NOTE SEE ITEMS ON A/2.0, A/2.1 AND A/3.0 ALSO |
| | CHECK WINDOW SIZES VERSES SCHEDULE MARK, SEE 2ND FL. |
| | RIGHT ELEVATION ALL WINDOWS ARE THE SAME SIZE YET HAVE |
| | DIFFERENT MARKS****** |
| | |
| | 12)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN |
| | THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING, |
| | THE NOTICE IS VOID. PLEASE RERECORD AND SUBMIT PRIOR TO |
| | PERMIT BEING ISSUED. |
| | |
| | NEW COMMENTS |
| | |
| | 1)NO DESIGN PRESSURES WERE GIVEN FOR THE FOLDING |
| | PANEL WALLS, PLEASE NOTE THE MAX. PRODUCT APPROVAL |
| | DESIGN PRESSURE IS -55 PSF. |
| | |
| | 2)NO DESIGN PRESSURE WAS GIVEN FOR THE FIXED WINDOW, |
| | PLEASE NOTE THAT NOT ALL GLASS TYPES WILL MEET THE |
| | PRESSURES REQUIRED BY SCHEDULE ON S/3 |
| | |
| | 3)DESIGN PRESSURES IN THE FRENCH DOOR PRODUCT |
| | APPROVALS ONLY MEET SCHEDULE ON S/3 WITH TYPE "A" |
| | GLASS. THIS IS ALSO THE CASE WITHSOME WINDOWS AND |
| | OTHERS WILL NOT MEET THE PRESSURES IN SCHEDULE AT ALL |
| | FOR EXAMPLE TYPES B,C AND E IN ZONE 5 AND TYPE G IN |
| | ZONE 4. |
| | |
| | 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING |
| | MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF |
| | ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND |
| | STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE |
| | DRAWINGS |
| | |
| | 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES |
| | ONLY FOR REFERENCE. NEW PAGES TO BE RESTAMPED BY |
| | HISTORIC |
| | |