2007-08-13 18:22:57 
  
 DENIED 2ND REVIEW
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT FULLY ADDRESSED
 ON THE FIRST REVIEW
  
 1)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 ******NOTE PRODUCT APPROVALS WERE NOT SUBMITTED FOR THE
 MULLIONS THAT ARE REQUIRED AT THE GREAT ROOM FRONT
 WINDOWS OR THE FRONT ENTRY DOOR******
  
 3)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 ****** NOTE: THESE PRODUCT APPROVALS CAN BE FOUND AT
 THE ABOVE WEB SITE, THE FL#'SARE WRITTEN AT THE TOP
 OF THE MIAMI-DADE REPORTS. PLEASE SEE THAT THE
 MIAMI-DADE NOA'S ARE IN THE CERTIFYING AGENCY FOR THE
 STATE APPROVALS AND WILL ALSO NEED TO BE SUBMITTED WITH
 THE STATE COVER SHEETS******
  
 4)MANY KEY NOTES ON ARCHITECTURAL SHEETS DO NOT
 CORRESPOND WITH DRAWINGS PLEASE CLARIFY
  
 ******NOTE SEE ITEMS ON A/2.0, A/2.1 AND A/3.0 ALSO
 CHECK WINDOW SIZES VERSES SCHEDULE MARK, SEE 2ND FL.
 RIGHT ELEVATION ALL WINDOWS ARE THE SAME SIZE YET HAVE
 DIFFERENT MARKS******
  
 12)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID. PLEASE RERECORD AND SUBMIT PRIOR TO
 PERMIT BEING ISSUED.
  
 NEW COMMENTS
  
 1)NO DESIGN PRESSURES WERE GIVEN FOR THE FOLDING
 PANEL WALLS, PLEASE NOTE THE MAX. PRODUCT APPROVAL
 DESIGN PRESSURE IS -55 PSF.
  
 2)NO DESIGN PRESSURE WAS GIVEN FOR THE FIXED WINDOW,
 PLEASE NOTE THAT NOT ALL GLASS TYPES WILL MEET THE
 PRESSURES REQUIRED BY SCHEDULE ON S/3
  
 3)DESIGN PRESSURES IN THE FRENCH DOOR PRODUCT
 APPROVALS ONLY MEET SCHEDULE ON S/3 WITH TYPE "A"
 GLASS. THIS IS ALSO THE CASE WITHSOME WINDOWS AND
 OTHERS WILL NOT MEET THE PRESSURES IN SCHEDULE AT ALL
 FOR EXAMPLE TYPES B,C AND E IN ZONE 5 AND TYPE G IN
 ZONE 4.
  
 4)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
 IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE. NEW PAGES TO BE RESTAMPED BY
 HISTORIC
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  