| 2007-06-26 15:55:24 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A-3.0: THE FOLLOWING NEW KEY NOTES ARE NOT |
| | BEING INDICATED ON THE NEW WORK FIRST FLOOR PLAN. |
| | A} #8 EXISTING SHOWER AND SHOWER DOOR TO REMAIN. |
| | B} #23 NEW GAS SERVICE AT FLOOR FOR NEW GAS RANGE. |
| | |
| | 2. SHEET P-1.0 SANITARY PIPING ISOMETRIC: PLEASE |
| | CORRECT THE FOLLOWING. |
| | A}MASTER BATH: THE LAV BY THE JACUZZI IS NOT |
| | VENTED. THE TRAP IS MORE THAN EIGHT FEET (8') FROM THE |
| | VENT. PER FBC-2004 PLUMBING TABLE 906.1, A2" FIXTURE |
| | DRAIN WITH AN 1-1/2" TRAP CAN ONLY BE 6' FROM THE VENT. |
| | AN AIR ADMITTANCE VALVE IS SUGGESTED PER FBC-2004 |
| | PLUMBING SECTION 917.3. |
| | B} PLEASE CLEARLY INDICATE WHAT "WSB" IS ON THE |
| | RESUBMITTAL. IS THIS THE WASHING MACHINE SUPPLY BOX? |
| | C} PER FBC-2004 PLUMBING SECTION, 708.9 ACCESS, PLEASE |
| | INDICATE THE CLEANOUT FOR THE WASHING MACHINE AT 4' |
| | A.F.F. |
| | D} PER FBC-2004 PLUMBING, SECTION 406.3 PLEASE |
| | INDICATE THE SIZE FOR THE WASHING MACHINE TRAP AND |
| | STANDPIPE TO BE 2". |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |