| Date |
Text |
| 2007-06-26 16:42:38 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.SHEET P-2.0 NATURAL GAS ISOMETRIC DOES NOT REFLECT |
| | THE FLOOR PLAN NATURAL GAS ON SHEET P-1.0, THE FLOOR |
| | PAN ON THAT SHEET INDICATES THE GAS METER AT ONE END |
| | WITH THE RANGE AND WATER HEATER AT THE OTHER. NOTE: THE |
| | ISOMETRIC ON SHEET P-2.0 IS INDICATING THE GAS METER |
| | BETWEEN THE TWO APPLIANCES. PLEASE CORRELATE THE TWO |
| | SHEETS ON THE RESUBMITTAL. |
| | |
| | 2. SHEET P-1.0 DRAWING NOTES #4 IS INDICATING FOR THE |
| | NEW RANGE, A NEW GAS LINE UNDER SLAB IN 4" SCH. 40 PVC |
| | CONDUIT WITH LONG SWEEP ELLS. THE GAS ISOMETRIC ON |
| | SHEET P-2.0 IS NOT REFLECTING THIS. PLEASE INDICATE THE |
| | SLEEVE ON THE RESUBMITTED GAS ISOMETRIC AND PLEASE |
| | PROVIDE A DETAIL OF THE SLEEVE COMPLIANT WITH FBC-2004 |
| | FUEL GAS SECTION 404.11 PIPING UNDERGROUND BENEATH |
| | BUILDINGS, WITH THE PIPING MATERIAL OF SCHEDULE 40 |
| | BLACK STEEL BEING USED AS INDICATED ON SHEET P-2.0. |
| | |
| | 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: CORRESPONDING LENGTHS ARE NOT BEING INDICATED FOR |
| | ALL CUT SECTIONS OF PIPE ON SHEET P-2.0. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THERE ARE TWO INDICATIONS OF PIPE LENGTHS BEING |
| | INDICATED ON SHEET P-2.0, ONE IS 30' OF 1" PIPE AND THE |
| | OTHER IS 100' OF 3/4" PIPE. UNTIL COMMENT #3 IS |
| | ADDRESSED THIS COMMENT CAN NOT BE VERIFIED. THE 100' OF |
| | 3/4" PIPE TO THE NEW RANGE CAN'T BE RIGHT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |