Plan Review Notes
Plan Review Notes For Permit 07051183
Permit Number 07051183
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-21 17:37:38 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE DESIGN PROFESSIONAL OR OWNER MUST ELECT THE
 LEVEL OF ALTERATION PURSUANT TO SECTIONS 303, 304 AND
 305 OF THE EXISTING BUILDING CODE. PLEASE DECLARE SAME
 ON THE PLAN.
  
 2} THERE ARE CONFLICTING NOTES ON THE RISER DIAGRAM,
 SHEET E-2.0. EXISTING STATED FOR THE RISER, AND
 "NEW"FEEDER AND METER, WHICH ALSO APPEARS TO BE A
 METER/MAIN COMBINATION. IF NEW PER 110.9 AND 110.10:
 OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.SHEET E-1.0 ALSO INDICATES
 EXISTING. PLEASE CORRELATE.
  
 3} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED
 IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE
 SAME ON THE PLANS TO SHOW COMPLIANCE.
  
 5} THE NEW WHIRLPOOL AND JACUZZI NOTED ON SHEET A-3.1
 DO NOT APPEAR IN THE PANEL SCHEDULE.
  
 6} NOTES #12 & 13 ON SHEET A-2.2 AND NOTE #26 ON SHEET
 A-4.0 REGARDING THE SERVICE CONDUCTORS , ARE
 CONFLICTING. SEE COMMENT #2.
 NOTE: IT APPEARS THAT THE NOTES ON SHEETS A-2.2 AND
 A-4.0, ARE REGARDING THE OTHERS SHEET.
  
 7} NOTE #5, SHEET E-1.0 REGARDING THE BRANCH CIRCUIT
 FOR THE DINING ROOM RECEPTACLE WOULD VIOLATE
 210.52(B)(1) AND (2), SMALL APPLIANCE WITH NO OTHER
 OUTLETS..
  
 NOTE THE RECESS FIXTURES MUST COMPLY WITH ARTICLE
 13-606.1ABC 1.2.4, FBC.
  
 THERE MAY BE ADDITIONAL COMMENTS DEPENDING ONTHE
 LEVEL OF ALTERATION THAT IS DECLARED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved