| 2008-01-02 08:10:10 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | THESE COMMENTS HAVE NOT BEEN ADDRESSED FROM THE | | | PREVIOUS REVIEW: | | | | | | 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15 | | | AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE | | | PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND | | | CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE | | | 680.43 FOR LOCATION AND PROTECTION (GFI). | | | * ALSO THE PANEL INDICATES A 2 POLE 30 AMP BREAKER. | | | CORRELATE AND CORRECT THE LOAD CALCULATIONS TO REFLECT | | | THE NAMEPLATE RATING. | | | | | | 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES | | | NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS.*THE | | | DISCONNECT LOCATION STILL DOES NOT HAVE THE REQUIRED | | | CLEARANCES. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|