Plan Review Notes
Plan Review Notes For Permit 07051171
Permit Number 07051171
Review Stop E
Sequence Number 2
Notes
Date Text
2008-01-02 08:10:10 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THESE COMMENTS HAVE NOT BEEN ADDRESSED FROM THE
 PREVIOUS REVIEW:
  
 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15
 AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE
 PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND
 CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE
 680.43 FOR LOCATION AND PROTECTION (GFI).
 * ALSO THE PANEL INDICATES A 2 POLE 30 AMP BREAKER.
 CORRELATE AND CORRECT THE LOAD CALCULATIONS TO REFLECT
 THE NAMEPLATE RATING.
  
 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES
 NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS.*THE
 DISCONNECT LOCATION STILL DOES NOT HAVE THE REQUIRED
 CLEARANCES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718