| Plan Review Notes For Permit 07051171 |
| Permit Number |
07051171 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-06-12 10:18:04 | | | | | | | DENIED/INCOMPLETE INFORMATION | | | | | | 1} THE PANEL SCHEDULE NOTE "PROVIDE 200 AMP SERVICE" IS | | | IN CONFLICT WITH THE RISER, WHICH INDICATES AN EXISTING | | | 150 AMP, AND NOTE AT THELOCATION ON THE PLAN ALSO | | | INDICATES 150 AMP. PLEASE CLARIFY. | | | | | | 2} CIRCUIT 14,16 FOR THE DISHWASHER/DISPOSAL INDICATE | | | TWO DIFFERENT AMPERAGES FOR THE OCP. | | | | | | 3} THE "JACCI" CIRCUIT ON THE SCHEDULE AT 1.5K, 15 | | | AMPS, IS NOT WHAT IS INDICATED AT THE LOCATION ON THE | | | PLAN AT 50 AMPS/220 VOLTS. VERIFY ACTUAL NAMEPLATE AND | | | CHANGE SCHEDULE/CALCULATIONS ACCORDINGLY. ALSO SEE | | | 680.43 FOR LOCATION AND PROTECTION (GFI). | | | | | | 4}THE DISCONNECT LOCATION FOR THE WATER HEATER DOES | | | NOT COMPLY WITH 110.26 CLEARANCE REQUIREMENTS. | | | | | | 5} RECEPTACLES MUST BE ADDED IN THE "ENTRY", BEDROOM | | | AND KITCHEN TO COMPLY WITH 221.52(A)(1) & (2). SEE | | | REVIEWED SET OF PLANS FOR APPROXIMATE LOCATIONS. | | | | | | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|