Plan Review Notes
Plan Review Notes For Permit 07051166
Permit Number 07051166
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-11 13:51:33*** DENIED ***
 1) CHANGES MAY NOT BE DONE TO PLANS AFTER ARCHITECT HAS
 SEALED THEM
  
 2) CHANGES TO PLANS CAN NOT BE IN PENCIL.
  
 3) PLEASE DO NOT HIGH LIGHT PLANS AS THE SECOND COPY
 CAN NOT BE READ.
  
 4) ALL GRILLS NEED TO SHOW THE GRILL SIZE.
  
 5) NOT ALL DUCTS ARE SHOWN ON PLANS.
  
 6) DUCT DESIGN IS DIFFICULT TO READ AS THEIR IS TO MUCH
 ELECTRICAL DESIGN ON THEM. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY. PER 2004 FBC 106.1.1.
  
 7) PLEASE SHOW WHICH AHU IS #1 AND #2.
  
 8) PLEASE SHOW THE CLOTHES DRYER VENT TERMINATION
 LOCATION ON PLANS, BE ADVISED IT MUST NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, PER 2004 FBC/M 501.2 .
  
 9) PLEASE SHOW HOW THE AIR IS RETURNING TO THE AHU'S.
  
 10)PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
 .