Plan Review Notes
Plan Review Notes For Permit 07051157
Permit Number 07051157
Review Stop E
Sequence Number 2
Notes
Date Text
2007-07-16 19:09:262007-07-16 19:09:26
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS REQUESTED
 TO SUBMIT SLAB/SITE DETAIL INDICATING ANY CONDUITS TO
 BE INSTALLED UNDER THE FOUNDATION/SITE PERMIT. THE
 RESPONSE LETTER MENTIONS TO SEE REV 3 DETAIL ON SHEET
 5.1, HOWEVER NO DETAIL WAS LOCATED.??
  
 **AS A NOTE, THE RISER IS SHOWING AN "EQUIPMENT
 GROUNDING CONDUCTOR" AHEAD OF THE NEW MAIN WHICH IS
 NOT PERMITTED PER 250.6 AND 250.24. AN EQUIPMENT
 GROUNDIGN CONDUCTOR IS ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-16 18:37:422007-07-16 18:37:42
 PLANS IN ELEC FOR REVIEW. PLANS WILL RETURN TO INCOMING
 WAITING FOR COMM BOARD ONCE REVIEW IS COMPLETED.