| Plan Review Notes For Permit 07051157 |
| Permit Number |
07051157 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-16 19:09:26 | 2007-07-16 19:09:26 | | | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS REQUESTED | | | TO SUBMIT SLAB/SITE DETAIL INDICATING ANY CONDUITS TO | | | BE INSTALLED UNDER THE FOUNDATION/SITE PERMIT. THE | | | RESPONSE LETTER MENTIONS TO SEE REV 3 DETAIL ON SHEET | | | 5.1, HOWEVER NO DETAIL WAS LOCATED.?? | | | | | | **AS A NOTE, THE RISER IS SHOWING AN "EQUIPMENT | | | GROUNDING CONDUCTOR" AHEAD OF THE NEW MAIN WHICH IS | | | NOT PERMITTED PER 250.6 AND 250.24. AN EQUIPMENT | | | GROUNDIGN CONDUCTOR IS ONLY INSTALLED AFTER THE FIRST | | | MEANS OF DISCONNECT. | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-07-16 18:37:42 | 2007-07-16 18:37:42 | | | PLANS IN ELEC FOR REVIEW. PLANS WILL RETURN TO INCOMING | | | WAITING FOR COMM BOARD ONCE REVIEW IS COMPLETED. |
|