| Notes |
| Date |
Text |
| 2007-06-22 11:27:28 | *** UNSAT*** | | | | | | 1) NOTE: PLEASE SUBMIT ELECTRICAL DETAILS FOR GROUNDING | | | ELECTRODE SYSTEM WHICH IS PART OF SLAB/FOOTINGS FOR THE | | | MAIN BUILDING. THIS SHOULD BE PART OF THE DESIGN FROM | | | THE ELECTRICAL DESIGNER OF RECORD FROM THE BUILDING | | | PERMIT APPLICATION. | | | 250.50, 250.32. | | | | | | 2) NOTE: PLEASE SUBMIT AN UNDERGROUND CONDUIT | | | LAYOUT/SCHEDULE FOR ALL CONDUITS BEING INSTALLED. FBC | | | 106.3.5.1.2, 106.1.2, NEC 2005 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|