Plan Review Notes
Plan Review Notes For Permit 07051157
Permit Number 07051157
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-27 11:55:07 
  
2007-06-22 10:47:03 
  
  
  
 IRON MOUNTAIN- FOUNDATION ONLY
  
 BUILDING PLAN REVIEW
 PERMIT: 07051157
 ADD: 3501 ELECTRONIC WAY
 CONT: EDWARDS CONSTRUCTION SERVICES
 TEL: (352)854-6266
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE TAKE NOTE OF SURVEY FROM GT SURVEYING HAS A
 RAISED SEAL BUT A PHOTO-COPIED SIGNATURE. SEE FLORIDA
 ADMINISTRATIVE CODE 61G17 AND FL S S 472.025 ABOUT
 ORIGINAL SIGNATURES.
  
 4) PLEASE TAKE NOTE THAT ARCHITECTURAL ALLIANCE, INC.
 LOST THEIR CERTIFICATE OF AUTHORIZATION 2-28-2001. SEE
 ATTACHMENT FROM THE DPBR WEBSITE.
  
 5) CS-1 PLAN REVIEW DATA INDICATES THE PLAN WAS
 DESIGNED TO THE 2004 FBC PLEASE SEE PLAN AS SUBMITTED
 AFTER DEC.8TH, 2006 ARE TO BE REVIEWED UNDER THE 2006
 FBC.
  
 6) CS-1 PLAN REVIEW DATA DECLARES THIS BUILDING AS A
 IIB BUILDING UNPROTECTED (1 STORY) FULLY SPRINKLED,
 NOTE THE COMMENTFOR UNLIMITED AREA FOR TYPE II
 BUILDINGS S OCCUPANCIES FOR FULLY SPRINKLED BUILDINGS
 FBC 507.2REQUIRES A 60'-0"CLEARANCE, WHICH THIS
 BUILDING DOES NOT HAVE. 507.4 DOES PROVIDE FOR REDUCED
 OPEN SPACE REQUIREMENTS BUT THE EXISTING BUILDING IS
 21.29' AWAY FROM THE PROPERTY LINE. PLEASE PROVIDE
 INCREASES FOR SPRINKLERS, ONE STORY AND ANY AREA
 INCREASES THAT CAN BE TAKEN PROVIDE CALCULATIONS FOR
 AREA MODIFICATIONS ON THE PLAN. TOTAL SQ FT UNDER TYPE
 II-B UNPROTECTED (S-1) IS 17,500 SQ FT.
  
 7)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8)THE CONTRACTOR HAS ELECTED TO APPLY FOR A
 FOUNDATION PERMIT, THE DETAIL SHEET S-3 INDICATES THIS
 TO BE A MONOLITHIC SLAB, AS DRAWN THE ELECTRICAL WILL
 NEED TO SEE COMPLIANCE WITH THE GROUNDING ELECTRODE
 SYSTEM REQUIRING AN ELECTRICAL PERMIT.
  
 9) THIS IS A COMPLETELY SEPARATE BUILDING FROM THE
 BUILDING IN FRONT, SO THERE WOULD ALSO NEED TO BE A
 RISER FOR THE FIRE SPRINKLERS PENETRATING THE
 MONOLITHIC SLAB.THE SAME MAY HOLD TRUE FOR PLUMBING
 AND MECHANICAL
  
 10PROVISO: THE SOILS REPORT ALSO INDICATES AREAS OF
 ORGANIC CONTENT. PROVIDE FROM THE SOILS ENGINEERS
 REPORTS FOR THE REMOVAL AND COMPACTION OF THE LIFTS TO
 THE SOILS ENGINEERS RECOMMENDATIONS.
  
 11PROVISO:109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PREFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE APPLICABLE
 PROPERTY OWNER, UNDER TERMS & CONDITIONS AGREEABLE TO
 THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE, WATER OR
 DRAINAGE RUN-OFF, DEBRIS, AND THE STORAGE OF
 CONSTRUCTION MATERIALS. NEWCONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIESRESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL
 AS A PERMIT CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE
 WITH THIS PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A LICENSED ENGINEER
 SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 12 PROVISO: 109.3.10.1 HURRICANE PROTECTION. IT SHALL
 BE UNLAWFUL FOR ANY PERSON TO ALLOWCONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 13 BUILDING PROVISO: 105.13. SPECIAL FOUNDATION PERMIT
 WHEN APPLICATION FOR A PERMIT TO ERECT OR ENLARGE A
 BUILDING HAS BEEN FILED, & PENDING ISSUANCE OF SUCH
 PERMIT, THE BUILDING OFFICIAL MAY, AT HIS/ HER
 DISCRETION, ISSUE A SPECIAL PERMIT FOR THE FOUNDATION
 ONLY, UPON WRITTEN REQUEST OF THE OWNER AND CONTRACTOR.
 THE
 HOLDER OF SUCH A SPECIAL PERMIT IS PROCEEDING AT HIS OR
 HER OWN RISK AND WITH OUT ASSURANCE THAT A PERMIT FOR
 THE REMAINDER OF THE WORK WILL BE GRANTED AND THAT
 CORRECTIONS WILL NOT BE REQUIRED IN ORDER TO MEET THE
 PROVISIONS OF THE TECHNICAL CODE.
  
 14 BUILDING PROVISO: THIS IS AT MINIMUM TYPE II-B
 BUILDING WHICH NORMALLY WOULD REQUIRE A RESIDENT
 INSPECTOR BY THE CITY?S ADMINISTRATIVE CODE 109.3.7(1),
 AT THIS TIME THE
 INSPECTION SERVICES MANAGER HAROLD PISKURA HAS DEEM IT
 UNNECESSARY. IF PROBLEMS DO OCCUR DURING THE TIME OF
 CONSTRUCTION THE CITY MAY ELECT TO HAVE SUCH INSPECTOR
 ON SITE.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]