Plan Review Notes
Plan Review Notes For Permit 07051156
Permit Number 07051156
Review Stop ENG
Sequence Number 4
Notes
Date Text
2007-11-09 11:00:46***** FAILED *****
  
  
 1.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE
 FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU
 CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION,
 FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION,
 PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO
 SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS
 HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD
 CALCULATION. FIRST FLOOR ELEVATION SHOULD BE HIGHER
 THAN MAX CROWN OF THE ROAD ELEVATION BY 1 FOOT,
 ATLEAST.
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
  
 3. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN
 CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.%
 OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS
 PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT
 TO BE TREATED. CHANGES AREMARKED IN YOUR CALS. SO,
 PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD
 CRITERIA.DO YOU KEEP ALL STORM WATER ON SITE??, OR
 GOES INTOANY CANAL? PLEASE EXPLAIN. PLEASE ALSO
 RESUBMIT GEO-TECH REPORT WITH WATER QUALITY CALS.
  
 4. PLEASE SHOW ON THE DRAWING THE SITE AREA, PERVIOUS,
 IMPERVIOUS AREAYOU ARE DEVELOPING FOR THIS PROJECT
 ONLY ? DO YOU HAVE LAKE? PLEASE MAKE SURE THE AREA YOU
 USED IN WATER QUALITY CALS DO MATCH WITH THE AREA YOU
 SHOW ON DRAWINGS.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723