Plan Review Notes
Plan Review Notes For Permit 07051156
Permit Number 07051156
Review Stop ENG
Sequence Number 3
Notes
Date Text
2007-09-28 10:55:18***** FAILED *****
  
  
 1. WE COULD NOT FIND THE DRAWINGIN YOUR SUBMITTAL
 1/A-2 FOR DUMPSTER DETAILS,PER MR. CAMERO'S RESPONE
 LETTER OF MAY 23. 07.
 2.PLEASE SHOW IN DOCUMENT, HOW DID YOU DETERMINE THE
 FIRST FLOOR ELEVATION? PLEASE SHOW IN CALS THAT YOU
 CONSIDERED,CENTER LINE OF ROAD , SIDEWALK ELEVATION,
 FL BLDG CODE, & FLOOD ZONE AREA OF THIS LOCATION,
 PLEASE SHOW ALL THESE IN YOUR DOCUMENT. PLEASEALSO
 SHOW IN YOUR CALCULATION THAT YOUR FLOOR ELEVATION IS
 HIGHENOUGH TO MEET5, 10, 25, 100 YEAR FLOOD
 CALCULATION. SFWMD ALSO CHECK FIRST FLOOR ELEVATION
 BEFORE WE APPROVE.
 3. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,
 4. INYOUR WATER QUALITY CALS ON 1ST PAGE, IN
 CALCULATION OF % IMPERVIOUSTHERE IS A MINOR ERROR.%
 OF IMPERVIOUS SHOULD BE = 1.02/1.91=0.53% IMPERVIOUS
 PER SFWMD PROCEDURE.SO,.53X2.5X4.736/12= 0.53 AC-FT
 TO BE TREATED. CHANGES ARE MARKED IN YOUR CALS. SO,
 PLEASE REVISE THIS CALCULATIONS.WE USE SFWMD
 CRITERIA. DETAIL OF CONTROL STRUCTURE ETC . DO YOU KEEP
 ALL STORM WATER ON SITE??, OR ANY CANAL? PLEASE
 EXPLAIN. PLEASE ALSO RESUBMIT GEO-TECH REPORT WITH
 WATER QUALITY CALS.
 5. PLEASE SHOW ON THE DRAWING THE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT ONLY ?ALSO, WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT., DO YOU
 HAVE LAKE? PLEASE MAKE SURE THE AREA YOU USED IN WATER
 QUALITY CALS DO MATCH WITH THE AREA YOU SHOW ON
 DRAWINGS.
 6. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVE AT
 CONSTRUCTION SERVICES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723