| Notes |
| Date |
Text |
| 2007-06-18 16:09:55 | PLAN REVIEW ONLY NOT FOR PERMIT. | | | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.1. | | | | | | 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS (MANUAL J | | | CALCULATIONS), SEE 2004 FBC 13-607.1.ABC.1 . | | | | | | 3) PLEASE SHOW ON MECHANICAL PLANS AN EQUIPMENT LISTING | | | WITH ALL PERTINENT INFORMATION. | | | | | | 4) PLEASE SHOW CLOTHES DRYER VENT TERMINATION ON | | | MECHANICAL PLANS (ALL UNITS), SEE 2004 FBC/R M1501. | | | | | | 5) SHOW ON MECHANICAL PLANS ALL BATHROOM EXHAUST FANS | | | AND THE CFM'S. | | | | | | 6) PLEASE PROVIDE RETURN AIR TO THE FIRST FLOOR OFFICE | | | (ALL UNITS),SEE 2004 FBC/R M1602.4. | | | | | | 7) SHOW HOW THE SECOND FLOOR RETURN AIR IS GETTING BACK | | | TO THE SECOND FLOOR AIR HANDLER UNIT (IF LOUVERED DOOR | | | PLEASE SHOW ON MECHANICAL PLANS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|