Plan Review Notes
Plan Review Notes For Permit 07051152
Permit Number 07051152
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-15 16:51:22 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. AND AIC RATING FOR EACH SERVICE.
  
 2} FOR THE PANEL SCHEDULE/LOAD CALCULATION THAT IS
 SUBMITTED WITH THIS SET.
 A) TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER
 210.11(C)(1), 220.52(A).
  
 B) BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3),
  
 C) LAUNDRY CIRCUIT PER 220.52(B), @ 1500 WATTS.
  
 D) DRYER MUST BE CALCULATED PER 220.54 @ 5000 WATTS.
 ALSO SEE THIS IS ON A 40 AMP BREAKER WITH A 900 WATT
 LOAD.
  
 F) 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 3} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 4} WATER HEATERS ARE REQUIRED TO HAVE
 DISCONNECTS.422.16.THERE IS A RECEPTACLE SYMBOL SHOWN.
  
 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ALL UNITS IN
 SPACING VIOLATION.
  
 6} SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE
 INSTALLED WITHIN A 914-MM (36-IN.) HORIZONTAL PATH FROM
 A DOOR TO A KITCHEN OR A BATHROOM CONTAINING A SHOWER
 OR TUB. 11.8.3.5(5) NFPA-72, 2002. PER 313.1 WILL BE
 REQUIRED ON THE SECOND FLOOR.
  
 7} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 NOTE: REFERENCING SHEET A1 "WALL LEGEND"PER 2704.1,
 2004 FBC, METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING. PLEASE SEE ARTICLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]