| 2007-06-15 16:51:22 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, |
| | PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS |
| | PER 106.3.5.4 FBC. AND AIC RATING FOR EACH SERVICE. |
| | |
| | 2} FOR THE PANEL SCHEDULE/LOAD CALCULATION THAT IS |
| | SUBMITTED WITH THIS SET. |
| | A) TWO SMALL APPLIANCE CIRCUITS ARE REQUIRED PER |
| | 210.11(C)(1), 220.52(A). |
| | |
| | B) BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), |
| | |
| | C) LAUNDRY CIRCUIT PER 220.52(B), @ 1500 WATTS. |
| | |
| | D) DRYER MUST BE CALCULATED PER 220.54 @ 5000 WATTS. |
| | ALSO SEE THIS IS ON A 40 AMP BREAKER WITH A 900 WATT |
| | LOAD. |
| | |
| | F) 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION |
| | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. |
| | |
| | 3} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING |
| | AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE |
| | LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT |
| | GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE |
| | GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE |
| | DWELLING. |
| | |
| | 4} WATER HEATERS ARE REQUIRED TO HAVE |
| | DISCONNECTS.422.16.THERE IS A RECEPTACLE SYMBOL SHOWN. |
| | |
| | 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ALL UNITS IN |
| | SPACING VIOLATION. |
| | |
| | 6} SMOKE ALARMS AND SMOKE DETECTORS SHALL NOT BE |
| | INSTALLED WITHIN A 914-MM (36-IN.) HORIZONTAL PATH FROM |
| | A DOOR TO A KITCHEN OR A BATHROOM CONTAINING A SHOWER |
| | OR TUB. 11.8.3.5(5) NFPA-72, 2002. PER 313.1 WILL BE |
| | REQUIRED ON THE SECOND FLOOR. |
| | |
| | 7} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. |
| | |
| | NOTE: REFERENCING SHEET A1 "WALL LEGEND"PER 2704.1, |
| | 2004 FBC, METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| | EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| | ENERGIZE THE FRAMING. PLEASE SEE ARTICLE. |
| | |