Plan Review Notes
Plan Review Notes For Permit 07051152
Permit Number 07051152
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-08 19:55:15 
  
 DENIED
  
 1)PROVIDE DESIGN PARAMETERS ON DRAWINGS THIS INCLUDES
 THE CODE CYCLE (2004 FBC W/ 2006 AMENDMENTS) AND THE
 TYPE OF CONSTRUCTION
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 4)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES,
 AND THE PRODUCT NOA THAT LISTS THE SYSTEM COMPONENTS/
 FASTENER LIST PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 5)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 7)PROVIDE 2 COPIES OF RECENT SURVEY THAT SHOWS ALL
 EXISTING AND PROPOSED WORK, COMPLETE WITH ALL FRONT,
 SIDE AND REAR SETBACKS FROM BUILDINGS AND EQUIPMENT.
  
 8)IN AREAS OF QUESTIONABLE SOILS AS SHOWN IN THE
 OFFICIAL ZONING MAP OF THE CITY OF WEST PALM BEACH, 2
 COPIES OF A SOIL TEST REPORT SHALL BE SUBMITTED PER
 R401.4
  
 9)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1
  
 10)SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 11)PROVIDE THEVALUATION ON THE PERMIT APPLICATION.
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST EXCLUDING
 LAND VALUE. OUR VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*. IF VALUE IS FOUND TO BE LOW ADJUSTMENTS
 WILL BE MADE AND FEES DUE.
  
 12)SUBMIT ENERGY CALC'S PER 13-101.2.2 FBC. BE SURE
 THAT THEY ARE SIGNED AND DATED BY PREPARER AND
 OWNER/AGENT PRIOR TO SUBMITTAL
  
 13)FOUNDATION PLAN SHALL CONTAIN NOTES FOR VAPOR
 BARRIER AND TERMITE SOIL TREATMENT PER R506.2.3 & R320
 FBC RES.
  
 14)PROVIDE NOTE AT ALL SHOWER DOORS TO MEET SAFETY
 GLAZING IN HAZARDOUS LOCATIONS PER R308.4 ALSO DOOR
 SCHEDULE ON A/3 SHOWS SHOWER DOORS AS 1 1/2" THICK AND
 THE WALK IN CLOSET AS 3/8" THICK
  
 15)PROVIDE SMOKE ALARMS AT EACH LEVEL PER R313.1 FBC
 RES.
  
 16)STAIR HANDRAIL/GUARDS SHALL NOT ALLOW THE PASSAGE
 OF A 4" SPHERE PER R312.2 FBC RES.
  
 17)SECOND FLOOR LINTEL MARKS ARE NOT ASSIGNED IN
 BUILDINGS 1 & 2 ON SHEET A/10
  
 18)LINTEL SCHEDULE SHOWS ALL SIZES AS 8F24 YET
 SECTIONS SHOW A 8F16 PLEASE CLARIFY
  
 19)SECOND FLOOR FRAMING PLAN ON A/10 DOES NOT
 DESIGNATE A BEAM SIZE
  
 20)PROVIDECOMPLETE CONNECTOR SCHEDULE WITH THE
 FLORIDA STATEWIDE APPROVAL NUMBERS (THIS SAVES PRINTING
 OF ALL PRODUCT APPROVALS FOR EACH CONNECTOR)
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A PERMIT BEING
 ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  