| Plan Review Notes For Permit 07051146 |
| Permit Number |
07051146 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-14 14:05:28 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | | | | 1.)ZONE 3 HAS A DESIGN PRESSURE REQUIREMENT OF -83.1 | | | IF IT IS IN EXPOSURE B; SEE FBC TABLE 1609.6.2.1(2). | | | THE ASSEMBLY HAS A LIMITATION OF -75, NO ENHANCED | | | FASTENING ALLOWED PER SYSTEM LIMITATION #1. | | | | | | 2.)PROVIDE A SITE PLAN SHOWING BUILDING LOCATION. | | | SEE FBC1609.6.2.1(2), DEFINITION OF EXPOSURE C.IF | | | THIS BUILDING IS EXPOSURE C, DESIGN PRESSURE OF -100.56 | | | IS REQUIRED FOR ZONE 3. | | | |
|