| 2007-11-01 17:54:39 | DENIED |
| | REFERENCE: FBC-2004 W/2006 AMENDMENTS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. SHT A-4 BREAK ROOM SINK SHALL BE ACCESSIBLE. PLEASE |
| | SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | & ALL SUBSECTIONS. SHOW AN ELEVATION FOR SINK. SECTION |
| | 106.1.2. |
| | ****RESPONSE NOTED, BUT SHOW COMPLIANCE FOR THE |
| | FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE - FORWARD APPROACH |
| | REQUIRED. NO CABINET DOORS ALLOWED |
| | C. 11-4.24.6 EXPOSED PIPES & SURFACES |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 4. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING |
| | FOUNTAIN. SHOW COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| | SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| | PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | ****RESPONSE NOTED, NOT ADDRESSED |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT AM-7 SANITARY PLUMBING RISER & TYPICAL RISER DO |
| | NOT REFLECT THE FLOOR PLAN, NOR DO THEY MEET CODE |
| | REQUIREMENTS. NO BREAK ROOM SINK IS SHOWN ON RISERS, |
| | WATER CLOSETS AND LAVS ARE BACK TO BACK, DRINKING |
| | FOUNTAINS ARE NOT VENTED. (SEE RED LINE EXAMPLE IF |
| | PIPING IS GOING OUT THE SIDE OF THE BUILDING). |
| | ****RESPONSE NOTED, BUT THE DRINKING FOUNTAINS ARE NOT |
| | VENTED AS SHOWN. (SEE RED LINE CORRECTIONS). |
| | |
| | 8. OK |
| | |
| | 9. SUBMIT A WATER RISER DIAGRAM THAT REFLECTS THE FLOOR |
| | PLAN. SECTION 106.3.5.1.3(3)(8)(10)(13). |
| | ****RESPONSE NOTED, BUT THE DRINKING FOUNTAINS ARE NOT |
| | INDICATED ON THE RISER DIAGRAM. |
| | |
| | 10. OK |
| | 11. OK |
| | |