| 2007-09-21 15:39:25 | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTE(S) FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO |
| | THE ENERGY CALCULATIONS AND COORDINATION WITH PLANS. |
| | PLEASE SEE FIXTURE *A* FOR EXAMPLE WHICH IS SHOWN AS |
| | 128 TOTAL WATTS ON FIXTURE LEGEND ON PLANS, YET IT |
| | SEEMS THIS SAME FIXTURE IN STORAGE AREA IS PLACED ON |
| | THE INPUT DATA REPORT AS 100WATTS. |
| | PLEASE SEE FIXTURE LEGEND FOR TYPE *A*. |
| | PLEASE ALSO SEE THE ELECTRICAL PLANS INCLUDE AN |
| | ELECTRICAL WATER HEATER YET THERE IS NONE ENTERED ON |
| | THE CALCULATIONS. |
| | **PLEASE SEE THE OWNER AGENT IS STILL NOT SIGNED. |
| | **PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THE METHOD |
| | BEING USED. SUBMITTED AS *A* FOR AN EXISTING BUILDING? |
| | |
| | ** THE ELECTRICAL PLANS ARE OK. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |