Plan Review Notes
Plan Review Notes For Permit 07051134
Permit Number 07051134
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-21 15:39:25 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTE(S) FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #2 WITH RESPECT TO
 THE ENERGY CALCULATIONS AND COORDINATION WITH PLANS.
 PLEASE SEE FIXTURE *A* FOR EXAMPLE WHICH IS SHOWN AS
 128 TOTAL WATTS ON FIXTURE LEGEND ON PLANS, YET IT
 SEEMS THIS SAME FIXTURE IN STORAGE AREA IS PLACED ON
 THE INPUT DATA REPORT AS 100WATTS.
 PLEASE SEE FIXTURE LEGEND FOR TYPE *A*.
 PLEASE ALSO SEE THE ELECTRICAL PLANS INCLUDE AN
 ELECTRICAL WATER HEATER YET THERE IS NONE ENTERED ON
 THE CALCULATIONS.
 **PLEASE SEE THE OWNER AGENT IS STILL NOT SIGNED.
 **PLEASE SEE MECHANICAL REVIEW COMMENTS FOR THE METHOD
 BEING USED. SUBMITTED AS *A* FOR AN EXISTING BUILDING?
  
 ** THE ELECTRICAL PLANS ARE OK.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  