Plan Review Notes
Plan Review Notes For Permit 07051134
Permit Number 07051134
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-27 16:54:04------------------DENIED--------------------
  
 FBC 2004 CODE FAMILYW/2006 REVISIONS
  
 1. ENERGY CALCULATIONS:
 A) THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH
 THE CODE, AS PER SECTION 553.907, FLORIDA STATUTES,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. FBC 13-103.1.2
 B) AN ACCURATELY COMPLETED FORM 400A-04R (GENERATED BY
 THE FLA/COM-2004 COMPUTER PROGRAM, VERSION 2.5)
 DEMONSTRATING THAT CODE COMPLIANCE HAS BEEN ACHIEVED
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL FOR METHOD
 A COMPLIANCE. CALCULATIONS SHALL BE PERFORMED FOR THE
 CLIMATE ZONE IN WHICH THE BUILDING WILL BE LOCATED AND
 ACCORDING TO THE PROCEDURES SPECIFIED FOR METHOD A IN
 THIS SUBCHAPTER. 13-400.3.A METHOD A FORMS.
 C) CALCULATIONS CLAIM 2500 S.F. OF UNCONDITIONED SPACE
 BUT PLANS DO NOT SHOW ANY SEMIEXTERIOR BUILDING
 ENVELOPE THAT SEPARATES THE CONDITIONED FROM THE
 UNCONDITIONED SPACE. SEE FBC 13-2 DEFINITIONS: BUILDING
 ENVELOPE (B). PROVIDE SEPARATION BETWEEN SPACES OR
 REVISE ENERGY CALCULATIONS AND COOLING LOAD
 CALCULATIONS TO INCLUDE ALL INTERIOR SPACES.
 D) IF ALL SPACES ARE TO BE CONSIDERED CONDITIONED,
 PLEASE SEE FBC 13-403.1 DOOR TYPES REGARDING BACK DOOR
 AND GARAGE TYPE DOOR.
  
 2. PLAN NIDICATES FIRE DAMPERS TO BE LOCATED IN THE
 RATED CEILING. IF DUCT IS TO BE ABOVE A RATED CEILING,
 WHERE DO THE DUCTS FROM THE A/C CLOSETS PENETRATE THE
 RATED CEILING? ARE FIRE DAMPERS ALSO NEEDED IN THESE
 LOCATIONS? THE SPECIFIC LOCATION AND INSTALLATION
 DETAILS OF EACH FIRE DOOR, FIRE DAMPER, CEILING DAMPER
 AND SMOKE DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED
 ON THE BUILDING PLANS BY THE DESIGNER. FBC,M 607.8
  
 3. BOTH AHUS ARE MARKED ON PLANS AS AHU #2. BOTH
 CONDENSERS ARE MARKED AS CU #1. PLEASE IDENTIFY
 EQUIPMENT ON PLANS CORRECTLY AND COORDINATE WITH
 ELECTRICAL PLANS. FBC 106.1.1
  
 4. SOUTH DUCT SYSTEM, PLEASE PROVIDE SIZES FOR ALL 9
 FLEX DUCTS.
  
 5. NORTH DUCT SYSTEM, PLAN STATES "8 24X24 LAY-IN..."
 BUT PLAN ONLY SHOWS 7 GRILLS, FLEX RUN-OUTS. WHICH IS
 CORRECT?
  
 6. NORTH SIDE AND SOUTH SIDE EXHAUST GRILLS AND OUTSIDE
 AIR LOUVERS ARE SHOWN OUTSIDE THE BUILDING IN MID-AIR.
 PLEASE CLARIFY. ALSO, THERE IS AN EXHAUST GRILL ON THE
 SOUTH SIDE OF THE BUILDING WHERE THERE IS NO EXHAUST
 FAN. PLEASE CLARIFY.
  
 7. EXTERIOR LOUVERS ARE SUBJECT TO THE FLORIDA PRODUCT
 APPROVAL SYSTEM PER FAC 9B-72. PLEASE PROVIDE PRODUCT
 APPROVAL SPECIFIC TO THE LOUVERS TO BE USED.
  
 8. ARE LOUVERS TO BE DUCTED TO UNITS OR OPEN TO THE
 CLOSET PLENUM? VENTILATION SYSTEMS SHALL BE DESIGNED TO
 BE CAPABLE OF REDUCING THE SUPPLY OF OUTDOOR AIR TO THE
 MINIMUM VENTILATION RATES REQUIRED BY SECTION 6.1.3 OF
 ASHRAE 62. SYSTEMS MAY BE DESIGNED TO SUPPLY OUTSIDE
 AIR QUANTITIES EXCEEDING MINIMUM LEVELS, BUT THEY SHALL
 BE CAPABLE OF OPERATING AT NO MORE THAN MINIMUM LEVELS
 THROUGH THE USE OF RETURN DUCTS, MANUALLY OR
 AUTOMATICALLY OPERATED CONTROL DAMPERS, FAN VOLUME
 CONTROLS, OR OTHER DEVICES. FBC 13-409.1.ABC.1.1
  
 9. A/C CLOSETS SHOW BLOCK WALL EXPOSED IN PLENUM AREAS.
 CAVITIES DESIGNED FOR AIR TRANSPORT SUCH AS MECHANICAL
 CLOSETS, CHASES, AIR SHAFTS, ETC. SHALL BE LINED WITH
 AN AIR BARRIER AND SEALED IN ACCORDANCE WITH SECTION
 410.1.ABC.3.7 AND SHALL BE INSULATED IN ACCORDANCE WITH
 SECTION 410.1.ABC.2 (MINIMUM R-8 FOR EXTERIOR WALLS).
 BUILDING CAVITIES WHICH WILL BE USED AS RETURN AIR
 PLENUMS SHALL BE LINED WITH A CONTINUOUS AIR BARRIER
 MADE OF DURABLE NONPOROUS MATERIALS. ALL PENETRATIONS
 TO THE AIR BARRIER SHALL BE SEALED WITH A SUITABLE
 LONG-LIFE MASTIC MATERIAL. FBC 13-410.1.ABC.3.6
  
 10. PLEASE SHOW MEANS AND LOCATION OF CONDENSATE
 DISPOSAL. PLANS INDICATE DISPOSAL IN PARKING LOT AREA.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE. FBC,M 307.2.1
  
 11. PLEASE SHOW MEANS OF SECONDARY OR AUXILIARY DRAIN
 PROTECTION IN ACCORDANCE WITH FBC,M 307.2.3.
  
 12. PLAN SHOWS CONDENSATE DRAIN LINE TO BE PVC.
 MATERIALS EXPOSED WITHIN PLENUMS SHALL BE
 NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 FBC,M 606.2.2.1
  
 13. BALANCED RETURN IS REQUIRED FROM BREAK ROOM AREAS
 PER FBC,M 601.4.
  
 14. PLEASE PROVIDE OUTDOOR AIR CALCULATIONS SHOWING
 OCCUPANCY CLASSIFICATION, OCCUPANT LOADS AND REQUIRED
 CFM IN ACCORDANCE WITH FBC,M TABLE 403.3. FBC 106.1.2
  
 15. PLEASE PROVIDE ENGINEERED SYSTEM WITH DETAIL
 DRAWING SHOWING DESIGN WIND LOADS AND REQUIRED
 ATTACHMENTS PER FBC,M 301.13, FBC SEC 1609 AND FBC
 106.1.2.
  