| 2007-06-23 20:44:42 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THE VERSION OF THE ENERGY |
| | CALCULATIONS IS NOT CORRECT. PLEASE BE SURE TO SEE THE |
| | FLA-COM EFFECTIVE DATE DECEMBER 8TH, 2006 WHICH SHOULD |
| | READ VERSION 3.0. |
| | PLEASE SEE THERE IS A CONFLICT IN THE CODE AS THE 2004 |
| | FBC W/2006 REVISIONS STATES VERSION 2.5. CONTACT HAS |
| | BEEN MADE TO THE STATE FOR THIS CONFLICT AND THE STATE |
| | HAS INFORMED THIS AHJ THE VERSION 3.0 SHOULD BE USED. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT MATCH WITH |
| | THE PLANS SUBMITTED. |
| | PLEASE SEE THE TYPE OF FIXTURES DOES NOT MATCH. |
| | PLEASE SEE THE NUMBER OF LUMINARIES DOES NOT MATCH. |
| | PLEASE SEE THE WATTAGE FOR LUMINARIES DOES NOT MATCH. |
| | PLEASE SEE THE TOTAL DO NO MATCH. |
| | PLEASE SEE THE FIGURES SHOWN FOR EXTERIOR LIGHTING DO |
| | NOT MATCH WITH PLANS. |
| | PLEASE SEE THE METHOD OF CONTROL WHICH IS SHOWN AS |
| | *MANUAL ON/OFF DOES NOT MATCH. |
| | PLEASE COORDINATE ALL OF THESE ITEMS WITH ELECTRICAL |
| | PLANS. |
| | PLEASE SEE 13-415.1.AB.1.1 ETC. |
| | PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON SHEETS. |
| | PLEASE SEE THE COVER SHEET ATTACHED WITH THE COLOR |
| | PHOTO-COPY OF THE PERSON RESPONSIBLE FOR THE ENERGY |
| | CALCULATIONS HAS BEEN REMOVED.MUST BE ORIGINAL AND ON |
| | THE ENERGY CALCULATIONS AS SUBMITTED. |
| | PLEASE SEE THE SECOND SHEET OF THE ENERGY CALCULATIONS |
| | SHALL BEAR THE PRINTED NAME, SIGNATURE, AND LICENSE |
| | INFORMATION IF QUALIFYING UNDER FS 489 AND EXEMPTIONS |
| | UNDER FS 481.229, 471.003. |
| | PLEASE SEE INFORMATION FOR THE ELECTRICAL ENGINEER IS |
| | NOT LISTED. |
| | 13-103.1.1.1 |
| | PLEASE PROVIDE A TYPICAL DETAIL FOR THE OS CONNECTIONS |
| | INCLUDING DETAIL FOR TIE IN OF EMERGENCY/EXIT LIGHTING |
| | (700.12F). THIS CAN BE THE SAME DETAIL. |
| | |
| | 3) NOTE: PLEASE SEE PLANS AS THERE APPEARS TO LIGHTING |
| | FIXTURES ON PLANS WHICH DO NOT SHOW THE TYPE, |
| | CIRCUITING, CONTROL ETC. |
| | PLEASE COMPLETE. |
| | FBC 106.1.2 |
| | NEC, 240.4,310.16, FBC CHAPTER 13 ETC. |
| | |
| | 4) NOTE: PLEASE CORRELATE A/C LOADS WITH THE MECHANICAL |
| | PLANSOR MECHANICAL TO COORDINATE WITH ELECTRICAL. |
| | PLEASE SEE THE LOADS FOR HEAT DO NOT MATCH AND IF USING |
| | THE LOADS ON MECHANICAL PLANS THE LOADS ON THE |
| | ELECTRICAL PLANS WILL SUBSTANTIALLY CHANGE. PLEASE |
| | REVISE LOAD CALCULATIONS, PLEASE REVISE CONDUCTORS, |
| | PLEASE REVIEW OVER CURRENT PROTECTION DEVICES ETC. |
| | PLEASE SEE AHU #1 WHICH SHOWS 5KW ON ONE PHASE AND |
| | APPEARS TO MISPRINT 500KVA ON THE SECOND PHASE. (PANEL |
| | SCHEDULE). |
| | 240.4, 310.16, 424.3B, 220. |
| | |
| | 5) NOTE: PLEASE SEE THAT BASED ON THE FIXTURES SHOWN ON |
| | PLANS AND FIXTURES IN BATHROOM, THE LIGHTING LEGEND |
| | ALONG WITH ENERGY CALCULATIONS ETC WILL NEED TO BE |
| | ADJUSTED AND UPDATED. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THERE ARE RECEPTACLES ON PLANS |
| | WHICH DO NOT SHOW CIRCUITING TO THEM. PLEASE COMPLETE |
| | ALL CIRCUITING. PLEASE SEE ONE SET HAS SOME OF THESE |
| | REDLINED AT LOCATIONS. |
| | |
| | 7) NOTE: PLEASE SEE SPACING FOR THE SHOW WINDOW |
| | RECEPTACLES. PLEASE SEE 210.62 AS THE LENGTHS OF THE |
| | WINDOWS EXCEED 12FT WHICH WOULD REQUIRE ONE ADDITIONAL |
| | RECEPTACLE AT EACH LOCATION. |
| | PLEASE BE SURE TO ADJUST ANY LOADS AS NEEDED. PLEASE |
| | SEE LOAD CALCULATIONS AS THE LOAD SHOWN MENTIONS 33 FT |
| | FOR THE TOTAL, HOWEVER BASED ON THE SCALE, THE LINEAR |
| | FT DOES NOT CORRELATE. |
| | PLEASE ADJUST. |
| | |
| | 8) NOTE: PLEASE STATE THE TYPE OF STORAGE AND ITEMS |
| | BEING SOLD (IF KNOWN AT THIS TIME). PLEASE SEE NEC 500 |
| | IF NEEDED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |