Plan Review Notes
Plan Review Notes For Permit 07051134
Permit Number 07051134
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-23 20:44:42*** UNSAT ***
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SEE THE VERSION OF THE ENERGY
 CALCULATIONS IS NOT CORRECT. PLEASE BE SURE TO SEE THE
 FLA-COM EFFECTIVE DATE DECEMBER 8TH, 2006 WHICH SHOULD
 READ VERSION 3.0.
 PLEASE SEE THERE IS A CONFLICT IN THE CODE AS THE 2004
 FBC W/2006 REVISIONS STATES VERSION 2.5. CONTACT HAS
 BEEN MADE TO THE STATE FOR THIS CONFLICT AND THE STATE
 HAS INFORMED THIS AHJ THE VERSION 3.0 SHOULD BE USED.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT MATCH WITH
 THE PLANS SUBMITTED.
 PLEASE SEE THE TYPE OF FIXTURES DOES NOT MATCH.
 PLEASE SEE THE NUMBER OF LUMINARIES DOES NOT MATCH.
 PLEASE SEE THE WATTAGE FOR LUMINARIES DOES NOT MATCH.
 PLEASE SEE THE TOTAL DO NO MATCH.
 PLEASE SEE THE FIGURES SHOWN FOR EXTERIOR LIGHTING DO
 NOT MATCH WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROL WHICH IS SHOWN AS
 *MANUAL ON/OFF DOES NOT MATCH.
 PLEASE COORDINATE ALL OF THESE ITEMS WITH ELECTRICAL
 PLANS.
 PLEASE SEE 13-415.1.AB.1.1 ETC.
 PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON SHEETS.
 PLEASE SEE THE COVER SHEET ATTACHED WITH THE COLOR
 PHOTO-COPY OF THE PERSON RESPONSIBLE FOR THE ENERGY
 CALCULATIONS HAS BEEN REMOVED.MUST BE ORIGINAL AND ON
 THE ENERGY CALCULATIONS AS SUBMITTED.
 PLEASE SEE THE SECOND SHEET OF THE ENERGY CALCULATIONS
 SHALL BEAR THE PRINTED NAME, SIGNATURE, AND LICENSE
 INFORMATION IF QUALIFYING UNDER FS 489 AND EXEMPTIONS
 UNDER FS 481.229, 471.003.
 PLEASE SEE INFORMATION FOR THE ELECTRICAL ENGINEER IS
 NOT LISTED.
 13-103.1.1.1
 PLEASE PROVIDE A TYPICAL DETAIL FOR THE OS CONNECTIONS
 INCLUDING DETAIL FOR TIE IN OF EMERGENCY/EXIT LIGHTING
 (700.12F). THIS CAN BE THE SAME DETAIL.
  
 3) NOTE: PLEASE SEE PLANS AS THERE APPEARS TO LIGHTING
 FIXTURES ON PLANS WHICH DO NOT SHOW THE TYPE,
 CIRCUITING, CONTROL ETC.
 PLEASE COMPLETE.
 FBC 106.1.2
 NEC, 240.4,310.16, FBC CHAPTER 13 ETC.
  
 4) NOTE: PLEASE CORRELATE A/C LOADS WITH THE MECHANICAL
 PLANSOR MECHANICAL TO COORDINATE WITH ELECTRICAL.
 PLEASE SEE THE LOADS FOR HEAT DO NOT MATCH AND IF USING
 THE LOADS ON MECHANICAL PLANS THE LOADS ON THE
 ELECTRICAL PLANS WILL SUBSTANTIALLY CHANGE. PLEASE
 REVISE LOAD CALCULATIONS, PLEASE REVISE CONDUCTORS,
 PLEASE REVIEW OVER CURRENT PROTECTION DEVICES ETC.
 PLEASE SEE AHU #1 WHICH SHOWS 5KW ON ONE PHASE AND
 APPEARS TO MISPRINT 500KVA ON THE SECOND PHASE. (PANEL
 SCHEDULE).
 240.4, 310.16, 424.3B, 220.
  
 5) NOTE: PLEASE SEE THAT BASED ON THE FIXTURES SHOWN ON
 PLANS AND FIXTURES IN BATHROOM, THE LIGHTING LEGEND
 ALONG WITH ENERGY CALCULATIONS ETC WILL NEED TO BE
 ADJUSTED AND UPDATED.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THERE ARE RECEPTACLES ON PLANS
 WHICH DO NOT SHOW CIRCUITING TO THEM. PLEASE COMPLETE
 ALL CIRCUITING. PLEASE SEE ONE SET HAS SOME OF THESE
 REDLINED AT LOCATIONS.
  
 7) NOTE: PLEASE SEE SPACING FOR THE SHOW WINDOW
 RECEPTACLES. PLEASE SEE 210.62 AS THE LENGTHS OF THE
 WINDOWS EXCEED 12FT WHICH WOULD REQUIRE ONE ADDITIONAL
 RECEPTACLE AT EACH LOCATION.
 PLEASE BE SURE TO ADJUST ANY LOADS AS NEEDED. PLEASE
 SEE LOAD CALCULATIONS AS THE LOAD SHOWN MENTIONS 33 FT
 FOR THE TOTAL, HOWEVER BASED ON THE SCALE, THE LINEAR
 FT DOES NOT CORRELATE.
 PLEASE ADJUST.
  
 8) NOTE: PLEASE STATE THE TYPE OF STORAGE AND ITEMS
 BEING SOLD (IF KNOWN AT THIS TIME). PLEASE SEE NEC 500
 IF NEEDED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.