| Plan Review Notes For Permit 07051114 |
| Permit Number |
07051114 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-10-20 12:14:49 | DENIED; | | | FROM PAST REVIEW; | | | 1. NO YES NOTE SHOWING VACUUM BREAKER CODES HELPS BUT | | | DOES NOT SHOW WERE REQUIRED. ALSO 608.15.4.1 REFURS TO | | | MANUFACTURE'S INSTRUCTIONS. (NOT SHOWN ON CUT SHEETS | | | PROVIDED) ADD NOT TO WATER RISER DIAGRAM "VACUUM | | | BREAKERS REQUIRED HERE" WITH AN ARROW. | | | 2. OK | | | 3.NO THE ADA DETAILS SHOWN DO NOT REFLECT THE FLOOR | | | PLAN. SHOW ONLY THE ADA DRINKING FOUNTAIN. THE BATHROOM | | | DETAIL SHOWN DOES NOT REFLECT THE FLOOR PLAN. | | | FROM LAST REVIEW; | | | 4.(F)ONE DRINKING FOUNTAIN IS PERMITED WITH A CUP | | | DISPENSOR INSTALLED. ( SHOW DISPENSOR ON PLANS) | | | 5. NO SINK NOT SHOWN ON RISER DIAGRAMS SANITARY AND | | | WATER. ALSO THE FLOOR PLAN SHOWS A 36" PLUMBERS WALL | | | FOR SHAMPOO SINKS BUT SANITARY RISER DIAGRAM SHOWS | | | SINKS ARE VENTED INTO THE CEILING. PLEASE CORRECT. | | | 6. OK | | | NEW COMMENTS; | | | 7.IS SINK, BEING MOVED, A BREAK SINK OR A WORK SINK? IF | | | A BREAK SINK IT MUST MEET ADA REQUIREMENTS ( SINCE IT | | | IS BEING RELOCATED) FBC BUILDING SECTIONS 11-4.24.1 | | | THRU 11-4.24.7. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | | | | |
|