| 2007-10-01 20:02:48 | 2007-10-01 20:02:48 |
| | |
| | ** DENIED 3RD REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE STILL COMMENTS FROM THE |
| | TWO PREVIOUS REVIEWS WHICH ARE THE EXACT SAME COMMENTS |
| | WHICH STILL NEED TO BE ADDRESSED. |
| | AS THE ELECTRICAL PLANS AS SUBMITTED HAVE NOW ONCE |
| | AGAIN CHANGED THE DESIGNER OF RECORD, THE FEE AS |
| | REQUIRED UNDER FLORIDA STATUTES 553.80(2)(B) IS NOT |
| | ASSESSED. |
| | THIS STATUTE IS IN PLACE WHEN PLANS ARE DENIED FOR THE |
| | *SAME CODE COMPLIANT* COMMENT THREE OR MORE TIMES. ONLY |
| | WHEN THE SAME DESIGNER OF RECORD HAS HAD THE SAME |
| | COMMENT IS THE FEE THEN ASSESSED. |
| | THIS IS NOTED AS THESE COMMENTS AND PLANS NEED TO BE |
| | ADDRESSED AND COORDINATED. |
| | |
| | 2) NOTE: PLEASE SEE AS CLEARLY STATED ON BOTH PREVIOUS |
| | REVIEWS: PLEASE SUBMIT A FIXTURE LEGEND/IDENTIFICATION |
| | AND CORRELATE WITH LIGHTING PERFORMANCE CALCULATIONS AS |
| | REQUIRED PER FLORIDA BUILDING CODE 13-415.2. PLEASE |
| | KNOW AS NO LIGHTING FIXTURE IDENTIFICATION AND |
| | CALCULATIONS WERE SUBMITTED, THE LIGHTING LEVELS CAN |
| | NOT BE REVIEWED OR CONFIRMED CODE COMPLIANT. |
| | ** IF THERE IS ANY PART OF THIS COMMENT NOT UNDERSTOOD, |
| | PLEASE CALL. |
| | |
| | 3) NOTE: PLEASE SEE AS STATED ON THE PREVIOUS REVIEWS, |
| | THE INSTANT WATER HEATING UNIT NEEDS TO CORRELATE WITH |
| | PLANS AND THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED. |
| | **PLEASE SEE THE SPECS/CUT SHEETS AS SUBMITTED CLEARLY |
| | SHOW THE NEAREST TANKLESS WATER HEATER UNIT IS 28.5 KW |
| | AND THIS UNIT IS SHOWN AS 1-PHASE 120/240VOLTS. |
| | ** THE PLANS INDICATE A 24KW 3-PHASE120/208V UNIT. |
| | PLEASE SEE AS THE LISTING CONTAINED ON THE SPECS/CUT |
| | SHEETS DO NOT INDICATE ANY UNIT FOR THIS SIZE AND |
| | VOLTAGE AS SHOWN ON PLANS/PANEL SCHEDULE AND LOAD |
| | CALCULATIONS, REVIEW AND CONFORMATION FOR CODE |
| | COMPLIANCE CAN NOT BE DONE. THESE SIMPLY JUST DO NOT |
| | MATCH. |
| | THE SPECS/CUT SHEETS EVEN STATE THREE INDEPENDENT |
| | BREAKERS?? |
| | PLEASE CORRELATE AND COORDINATE ALL. |
| | NEC 220, 110.3, 90.7. |
| | |
| | 4) NOTE: PLEASE CLARIFY HOW THE LOADS FOR THE |
| | RECEPTACLES WHICH ARE BEING DEDICATED TO HAIR BLOW |
| | DRYERS AND OTHER DEVICES CAN BE SHOWN WITH A STANDARD |
| | VA OF 180VA FOR GENERAL USE? (ACTUAL 200VA SHOWN ON |
| | PANEL) |
| | PLEASE SEE NEC 220 AND PLEASE CLARIFY LOADS. |
| | |
| | ** AS STATED ON PREVIOUS REVIEW: |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |