Plan Review Notes
Plan Review Notes For Permit 07051114
Permit Number 07051114
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-01 20:02:482007-10-01 20:02:48
  
 ** DENIED 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE THERE ARE STILL COMMENTS FROM THE
 TWO PREVIOUS REVIEWS WHICH ARE THE EXACT SAME COMMENTS
 WHICH STILL NEED TO BE ADDRESSED.
 AS THE ELECTRICAL PLANS AS SUBMITTED HAVE NOW ONCE
 AGAIN CHANGED THE DESIGNER OF RECORD, THE FEE AS
 REQUIRED UNDER FLORIDA STATUTES 553.80(2)(B) IS NOT
 ASSESSED.
 THIS STATUTE IS IN PLACE WHEN PLANS ARE DENIED FOR THE
 *SAME CODE COMPLIANT* COMMENT THREE OR MORE TIMES. ONLY
 WHEN THE SAME DESIGNER OF RECORD HAS HAD THE SAME
 COMMENT IS THE FEE THEN ASSESSED.
 THIS IS NOTED AS THESE COMMENTS AND PLANS NEED TO BE
 ADDRESSED AND COORDINATED.
  
 2) NOTE: PLEASE SEE AS CLEARLY STATED ON BOTH PREVIOUS
 REVIEWS: PLEASE SUBMIT A FIXTURE LEGEND/IDENTIFICATION
 AND CORRELATE WITH LIGHTING PERFORMANCE CALCULATIONS AS
 REQUIRED PER FLORIDA BUILDING CODE 13-415.2. PLEASE
 KNOW AS NO LIGHTING FIXTURE IDENTIFICATION AND
 CALCULATIONS WERE SUBMITTED, THE LIGHTING LEVELS CAN
 NOT BE REVIEWED OR CONFIRMED CODE COMPLIANT.
 ** IF THERE IS ANY PART OF THIS COMMENT NOT UNDERSTOOD,
 PLEASE CALL.
  
 3) NOTE: PLEASE SEE AS STATED ON THE PREVIOUS REVIEWS,
 THE INSTANT WATER HEATING UNIT NEEDS TO CORRELATE WITH
 PLANS AND THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED.
 **PLEASE SEE THE SPECS/CUT SHEETS AS SUBMITTED CLEARLY
 SHOW THE NEAREST TANKLESS WATER HEATER UNIT IS 28.5 KW
 AND THIS UNIT IS SHOWN AS 1-PHASE 120/240VOLTS.
 ** THE PLANS INDICATE A 24KW 3-PHASE120/208V UNIT.
 PLEASE SEE AS THE LISTING CONTAINED ON THE SPECS/CUT
 SHEETS DO NOT INDICATE ANY UNIT FOR THIS SIZE AND
 VOLTAGE AS SHOWN ON PLANS/PANEL SCHEDULE AND LOAD
 CALCULATIONS, REVIEW AND CONFORMATION FOR CODE
 COMPLIANCE CAN NOT BE DONE. THESE SIMPLY JUST DO NOT
 MATCH.
 THE SPECS/CUT SHEETS EVEN STATE THREE INDEPENDENT
 BREAKERS??
 PLEASE CORRELATE AND COORDINATE ALL.
 NEC 220, 110.3, 90.7.
  
 4) NOTE: PLEASE CLARIFY HOW THE LOADS FOR THE
 RECEPTACLES WHICH ARE BEING DEDICATED TO HAIR BLOW
 DRYERS AND OTHER DEVICES CAN BE SHOWN WITH A STANDARD
 VA OF 180VA FOR GENERAL USE? (ACTUAL 200VA SHOWN ON
 PANEL)
 PLEASE SEE NEC 220 AND PLEASE CLARIFY LOADS.
  
 ** AS STATED ON PREVIOUS REVIEW:
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]