Plan Review Notes
Plan Review Notes For Permit 07051114
Permit Number 07051114
Review Stop P
Sequence Number 2
Notes
Date Text
2007-08-21 10:16:52DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
 ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK** WATER RISER REQUIRED. FBC-2004
 ADMINISTRATION CODE SECTION 106.3.5.1(3).
 NOTE: THE RESUBMITTED WATER RISER DIAGRAM NEED TO
 INDICATE THE REQUIRED ATMOSPHERIC VACUUM BREAKERS PER
 FBC-2004 PLUMBING SECTION 608.13.6 FOR THE PROPOSED
 PORTABLE SHAMPOO CHAIRS W/SINK. THEY NEED TO BE LOCATED
 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE SHAMPOO SINKS
 AND NOTED AS SUCH ON THE WATER RISER.
  
 2. **OK**
  
 3. **NO** SHOW ON THE PLAN COMPLIANCE WITH THE
 ACCESSIBILITY CODEBUILDING CHAPTER 11 SECTION
 11-4.1.6(2) 20% RULE.
 NOTE: PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS PER FBC-2004 CHAPTER 11.
  
 **WATER CLOSETS
 A} 11-4.16 WATER CLOSETS, ELEVATION DETAIL REQUIRED.
  
 B} 11-4.16.2 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR
 PLAN SHEET A-1)
  
 C} 11-4.16.3 HEIGHT.
  
 D} 11.4.16.4 GRAB BARS.
  
 E} 11-4.16.5 FLUSH CONTROLS.
  
 F} 11-4.16.6 DISPENSERS.
  
 **LAVATORIES AND MIRRORS
 A} 11-4.19 LAVATORIES, ELEVATION DETAIL REQUIRED.
  
 B} 11-4.19.2 HEIGHT AND CLEARANCES.
  
 C} 11-4.19.3 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR
 PLAN SHEET A-1)
  
 D} 11-4.19.4 EXPOSED PIPES AND SURFACES.
  
 E} 11-4.19.5 FAUCETS.
  
 F} 11-4.19.6 MIRRORS.
  
 **THE FOLLOWING ARE NEW ITEMS:
  
 4. PER FBC-2004 PLUMBING, TABLE 403.1 A DRINKING
 FOUNTAIN IS REQUIRED AND MUST BE ADA COLMPLIANT PER
 FBC-2004 CHAPTER 11.
  
 A} 11-4.15 DRINKING FOUNTAIN, ELEVATION DETAIL
 REQUIRED.
  
 B} 11-4.15.2 SPOUT HEIGHT.
  
 C} 11-4.15.3 SPOUT LOCATION.
  
 D} 11-4.15.4 CONTROLS.
  
 E} 11-4.15.5 CLEARANCES.(ALSO INDICATE CLEAR FLOOR
 SPACE ON FLOOR PLAN SHEET A-1)
  
 F} 11-4.1.3(10)(A)WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 5. SHEET A-1 SANITARY RISER DIAGRAM: THE RESUBMITTED
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE
 BATHROOM. PER 106.1.1 RISER DIAGRAM SHALL REFLECT THE
 FLOOR PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS
 INDICATING THIS AND CORRECT FOR THE RESUBMITTAL.
  
 6. SHEET A-1 SANITARY RISER DIAGRAM: THE WATER CLOSET
 DOES NOT NEED A TRAP IT HAS AN INTEGRAL TRAP. PER
 FBC-2004 PLUMBING SECTION 1002.1 A FIXTURE SHALL NOT BE
 DOUBLE TRAPPED.
  
 7. SHEET A-1 SANITARY RISER DIAGRAM: A VENT IS
 REQUIRED FOR THE PROPOSED PORTABLE SHAMPOO CHAIRS
 W/SINKS PER FBC-2004 PLUMBING SECTION 901.2.1.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE
 INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM
 WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON
 THE INDICATED SHEETS BY THIS PLAN EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved