| Date |
Text |
| 2007-08-21 10:16:52 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | ** FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY CODE. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| | SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| | REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| | MADE ON PREVIOUS REVIEWS. |
| | |
| | ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| | THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| | PREVIOUS REVIEW NOTES. |
| | |
| | A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| | FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| | ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| | EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| | |
| | AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| | COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| | |
| | A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| | ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| | COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| | |
| | ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| | THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| | |
| | 1. **NO/OK** WATER RISER REQUIRED. FBC-2004 |
| | ADMINISTRATION CODE SECTION 106.3.5.1(3). |
| | NOTE: THE RESUBMITTED WATER RISER DIAGRAM NEED TO |
| | INDICATE THE REQUIRED ATMOSPHERIC VACUUM BREAKERS PER |
| | FBC-2004 PLUMBING SECTION 608.13.6 FOR THE PROPOSED |
| | PORTABLE SHAMPOO CHAIRS W/SINK. THEY NEED TO BE LOCATED |
| | 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE SHAMPOO SINKS |
| | AND NOTED AS SUCH ON THE WATER RISER. |
| | |
| | 2. **OK** |
| | |
| | 3. **NO** SHOW ON THE PLAN COMPLIANCE WITH THE |
| | ACCESSIBILITY CODEBUILDING CHAPTER 11 SECTION |
| | 11-4.1.6(2) 20% RULE. |
| | NOTE: PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE |
| | RESUBMITTED PLANS PER FBC-2004 CHAPTER 11. |
| | |
| | **WATER CLOSETS |
| | A} 11-4.16 WATER CLOSETS, ELEVATION DETAIL REQUIRED. |
| | |
| | B} 11-4.16.2 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR |
| | PLAN SHEET A-1) |
| | |
| | C} 11-4.16.3 HEIGHT. |
| | |
| | D} 11.4.16.4 GRAB BARS. |
| | |
| | E} 11-4.16.5 FLUSH CONTROLS. |
| | |
| | F} 11-4.16.6 DISPENSERS. |
| | |
| | **LAVATORIES AND MIRRORS |
| | A} 11-4.19 LAVATORIES, ELEVATION DETAIL REQUIRED. |
| | |
| | B} 11-4.19.2 HEIGHT AND CLEARANCES. |
| | |
| | C} 11-4.19.3 CLEAR FLOOR SPACE.(ALSO INDICATE ON FLOOR |
| | PLAN SHEET A-1) |
| | |
| | D} 11-4.19.4 EXPOSED PIPES AND SURFACES. |
| | |
| | E} 11-4.19.5 FAUCETS. |
| | |
| | F} 11-4.19.6 MIRRORS. |
| | |
| | **THE FOLLOWING ARE NEW ITEMS: |
| | |
| | 4. PER FBC-2004 PLUMBING, TABLE 403.1 A DRINKING |
| | FOUNTAIN IS REQUIRED AND MUST BE ADA COLMPLIANT PER |
| | FBC-2004 CHAPTER 11. |
| | |
| | A} 11-4.15 DRINKING FOUNTAIN, ELEVATION DETAIL |
| | REQUIRED. |
| | |
| | B} 11-4.15.2 SPOUT HEIGHT. |
| | |
| | C} 11-4.15.3 SPOUT LOCATION. |
| | |
| | D} 11-4.15.4 CONTROLS. |
| | |
| | E} 11-4.15.5 CLEARANCES.(ALSO INDICATE CLEAR FLOOR |
| | SPACE ON FLOOR PLAN SHEET A-1) |
| | |
| | F} 11-4.1.3(10)(A)WHERE ONLY ONE DRINKING FOUNTAIN IS |
| | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN |
| | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS |
| | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE |
| | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 5. SHEET A-1 SANITARY RISER DIAGRAM: THE RESUBMITTED |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE |
| | BATHROOM. PER 106.1.1 RISER DIAGRAM SHALL REFLECT THE |
| | FLOOR PLAN. PLEASE REFERENCE THE RED LINE CORRECTIONS |
| | INDICATING THIS AND CORRECT FOR THE RESUBMITTAL. |
| | |
| | 6. SHEET A-1 SANITARY RISER DIAGRAM: THE WATER CLOSET |
| | DOES NOT NEED A TRAP IT HAS AN INTEGRAL TRAP. PER |
| | FBC-2004 PLUMBING SECTION 1002.1 A FIXTURE SHALL NOT BE |
| | DOUBLE TRAPPED. |
| | |
| | 7. SHEET A-1 SANITARY RISER DIAGRAM: A VENT IS |
| | REQUIRED FOR THE PROPOSED PORTABLE SHAMPOO CHAIRS |
| | W/SINKS PER FBC-2004 PLUMBING SECTION 901.2.1. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS WHICH HAVE CHANGED, PLEASE |
| | INCLUDE A TRANSMITTAL LETTER INDICATING HOW EACH ITEM |
| | WAS ADDRESSED AND PROVIDE ONE COPY OF ALL OLD/VOIDED |
| | SHEETS FOR REFERENCE ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK ON |
| | THE INDICATED SHEETS BY THIS PLAN EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |
| | |