Plan Review Notes
Plan Review Notes For Permit 07051114
Permit Number 07051114
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-10 21:13:15 
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL NEEDING TO BE ADDRESSED ALONG WITH NEW COMMENTS
 DUE TO CHANGES ON PLANS AND NEW INFORMATION ONLY NOW
 SUBMITTED FOR REVIEW.
  
  
 1) NOTE: PLEASE SEE A FOUR TIMES THE PERMIT FEE WAS
 ASSESSED FOR COMMENCING WORK WITHOUT PERMITS AS
 REQUIRED PER FBC 105.1 AND 108.4
 PLEASE KNOW THE BALANCE IS DUE AT THIS TIME. THE
 CONTRACTOR WAS CONTACTED AND INFORMATION OF THIS AS OF
 THIS REVIEW.
  
 2) NOTE: PLEASE SEE THAT THE SCOPE OF WORK BEING
 APPLIED FOR IS APPLIED UNDER OF CERTIFIED RESIDENTIAL
 CONTRACTOR (CRC) WHICH DOES NOT PERMIT THIS LICENSE TO
 DO WORK IN A COMMERCIAL BUILDING. THIS WAS CONFIRMED
 WITH THE PALM BEACH COUNTY LICENSING BOARD AS WELL AS
 WITH INFORMATION WITH THE STATE OF FLORIDA LICENSING
 BOARD. PLEASE APPLY UNDER A LICENSE WHICH PERMITS THIS
 SCOPE OF WORK OR PLEASE KNOW THIS PERMIT WILL BE
 REQUIRED TO BE APPLIED FOR UNDER LICENSE CONTRACTOR
 WHOM CAN PERFORM THIS WORK.
 PLEASE KNOW A MESSAGE WAS LEFT FOR THE CONTRACTOR BY
 THE INSPECTION SERVICES MANAGER FOR THE QUALIFIER TO
 CONTACT THIS OFFICE.
 CHAPTER 67-1876 AS AMENDED BY THE PALM BEACH COUNTY
 LICENSING BOARD.
 FLORIDA STATUTES 489
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS ARE NOW COMING
 IN UNDER A NEW DESIGNER AND THE DESIGNER OF RECORD AS
 SHOWN IS PERMITTED TO DESIGN THE SCOPE AS SHOWN HOWEVER
 THE PLANS MUST CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND DEISGN.
 FS 489, 468
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW
 PLEASE INDICATE THE MAXIMUM TIMES ON OVER RIDES DEVICES
 AS REQUIRED PER 13-415.1.ABC.1.1 OF THE FBC. THIS WOULD
 BE FOR ALL DEVICES. ONLY TWO SHOWN ON DETAIL, YET PLANS
 INDICATE MORE.
 PLEASE ALSO SEE MISSING CONTROLS FOR SEPARATE SPACES
 PER 13-415.1.ABC.1.1 AND .1.2. THESE ARE SHOWN AS
 STANDARD SWITCHES.
 PLEASE SEE THE DETAIL AS SUBMITTED DOES NOT PROVIDE
 ENOUGH INFORMATION FOR SCOPE OF LIGHTING CONTROL
 SYSTEM. PLEASE SEE THAT THE LOCATION OF THE EQUIPMENT
 IS NOT SHOWN.
 PLEASE PROVIDE THE SCHEDULE OF TIMES AND LISTING OF THE
 CIRCUITS ON THE LIGHTING CONTACTOR AS SHOWN.
 ** PLEASE COORDINATE ALL OF THESE ITEMS AS SHOWN ON THE
 E-SHEET.
 PLEASE ALSO SEE THAT NO PERFORMANCE CALCULATIONS WERE
 SUBMITTED AND NO FIXTURE LEGEND TO COORDINATE WITH THE
 CALCULATIONS AND PLANS.
 13-415.2
 ** PLEASE SEE THE INFORMATION BELOW IN THIS SAME NOTE
 IS TAKEN FROM PREVIOUS REVIEW**
  
 PLEASE SEE FBC 2004 W/2006 REVISIONS AND CHAPTER 13.
 THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, 2005 WHICH
 REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE
 INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS
 WHICH COULD NOT BE LOCATED ON PLANS.
 ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR
 MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE,
 HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED.
  
 4) NOTE: PLEASE SEE NO REVISIONS WERE MADE TO THE
 APPLIED SCOPE OF WORK WHEN THE SCOPE OF WORK HAS
 INCREASED BASED ON CHANGES ON PLANS.
 RESPONSE FROM ENGINEER STATES THIS IS ADDRESS ON
 ELECTRICAL SHEETS. THIS IS UNCLEAR HOW THE VALUE FOR
 THE SCOPE OF WORK WOULD BE ON PLANS?
  
 ** PREVIOUS REVIEW NOTE ** PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK AS APPLIED WILL NEED TO BE
 REVISED BASED ON THE COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 5) NOTE: PLEASE SEE THE INFORMATION ON THE INSTA-HOT
 WATER HEATER IS NOW PROVIDED WHICH ACTUALLY CONFLICTS
 WITH THE PLANS AS SUBMITTED.
 PLEASE SEE THE MANUFACTURES SPECS/CUT SHEETS CLEARLY
 SHOWS THIS UNIT AS A 240V SINGLE PHASE AND THE SERVICE
 IT IS BEING ADDED TO IS A THREE PHASE 120/208V SERVICE.
 THIS IS BEING SHOWN AS A LISTED UNTI FOR 240V NOT
 208V.
 PLEASE SEE THE LOADS DO NOT CORRELATE ON PANEL
 SCHEDULE: FOR EXAMPLE, PLEASE SEE ONLY 28KW IS SHOWN ON
 PANEL SCHEDULE WHEN UNIT IS 28.5 KW ON SPECS/CUT
 SHEETS.
 PLEASE SEE THE LOAD ON THE LOAD CALCULATIONS ALSO DOES
 NOT CORRELATE AS THIS IS SHOWN AS 21KW.
 PLEASE SEE THE MINIMUM OVER CURRENT PROTECTION ON PANEL
 SCHEDULE IS SHOWN AS A 3-POLE 40AMP BREAKER. HOW IS
 THIS POSSIBLE WITH THE LOAD AS SHOWN?
 PLEASE SEE THE SPECS/CUT SHEETS CALL FOR MULTIPLE
 BREAKERS FOR MOST OF THE UNITS AS SHOWN.
 PLEASE INDICATE THE LOCATION OF THIS UNIT.
  
 ** THERE ARE SEVERAL ITEMS ON THIS UNIT WHICH DOES NOT
 AND WILL NOT MEET THE MINIMUM REQUIREMENTS OF THE NEC.
 240.4, 310.16, 422.13, 110.3, 90.7, ETC.
  
 6) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD.
 THIS WAS A COMMENT ON THE PREVIOUS REVIEW AND STILL
 REMAINS.
 PLEASE SEE THE AHU IS NOW SHOWN AS 5KW, YET THE PANEL
 SCHEDULE ALSO SHOWS ONLY 1.0KW FOR EACH PHASE. HOW IS
 THIS POSSIBLE?
 PLEASE SEE THE LOAD ON THE CU APPEARS TO BE HIGHER
 WHICH IS OK, HOWEVER THE HIGHER OF THE TWO LOADS OF AN
 A/C SYSTEM IS TO BE FIGURED ON THE LOAD CALCULATIONS.
 PLEASE SEE THE PANEL SCHEDULE INDICATES A TOTAL OF 6.6
 KW AND THE LOAD CALCULATIONS INDICATE A LOWER NUMBER
 JUST OVER 4KW.
 PLEASE CORRELATE AS THE LOAD CALCULATIONS AS SHOWN DO
 NOT MEET THE MINIMUM LOADS PER THE NATIONAL ELECTRICAL
 CODE.
 PLEASE CORRELATE ALL OTHER LOADS ON PANEL SCHEDULE WITH
 THAT AS SHOWN IN THE LOAD CALCULATIONS. PLEASE SEE
 ANOTHER FOR EXAMPLE: SIGN CIRCUITS PER 600.5, SCHEDULE
 SHOWS THE CORRECT 1200VA FOR EACH HOWEVER THE
 CALCULATIONS ONLY INCLUDE ONE.
 PLEASE SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN
 AND FIGURED AT 125%.
 PLEASE SEENEC 220AND COORDINATE AS THERE ARE
 SEVERAL SECTIONS OF 220 WHICH APPLY.
 215.3, 230.42 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE THE RECEPTACLE NEXT TO THE SINK IN
 AREA NEXT TO BATHROOM IS NOT GFI AS REQUIRED PER
 210.8B
  
 8) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON
 PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION
 NEEDS TO BE UPDATE ON PERMIT APPLICATION. THIS THE SAME
 COMMENT AS NO INFORMATION WAS CHANGED.
  
 9) NOTE: PLEASE KNOW DUE TO THE EXTENT OF THE COMMENTS,
 PERMIT APPLICATION AND SUBMITTED INFORMATION, MOST OF
 THESE DOCUMENTS WILL BE RETAINED BY THIS OFFICE.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE
 BEING SHOWN ON THE SAME PAGE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]