| 2007-06-10 08:55:32 | ** UNSAT ** |
| | |
| | |
| | ** PLEASE KNOW AS THERE AREITEMS ON PLANS WHICH WERE |
| | NOT SUBMITTED IN THE DESIGN FOR REVIEW, A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. |
| | PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE |
| | RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE |
| | CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS |
| | OF DECEMBER 8TH, 2006. |
| | PLEASE LIST THE FOLLOWING. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC) 2002 SHOWN. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | THIS IS REQUIRED AT A MINIMUM ON |
| | ARCHITECTURAL/ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE SEE FS 481.229 AS A DRAFTING FIRM MAY |
| | NOT PRODUCE DOCUMENTS FOR THIS SCOPE OF WORK. THE |
| | ENGINEER AS STATED ON PLANS IS NOTED AS CIVIL AND |
| | STRUCTURAL, PLEASE SEE FS 471.025 FOR SCOPE OF WORK |
| | PERMITTED UNDER SPECIFIC LICENSE AND SCOPE OF |
| | KNOWLEDGE. |
| | PLEASE CONTACT THE STATE BOARD OF ENGINEERS FOR FURTHER |
| | QUESTIONS FOR THE SCOPE OF WORK UNDER ENGINEER. PLEASE |
| | CONTACT THE STATE BOARD OF ARCHITECTS LEGAL COUNSEL FOR |
| | ANY FURTHER QUESTIONS. |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL RISER AS SHOWN ON |
| | PLANS DOES NOT CORRELATE WITH THE ACTUAL SERVICE AT |
| | LOCATION OF JOBSITE. PLEASE SHOW SERVICE AT LOCATION OF |
| | THIS BUILDING. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 215.5 |
| | |
| | 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND |
| | CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST, |
| | 2005 WHICH REQUIRED LIGHTING CONTROLS. |
| | A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE |
| | WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED |
| | LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF |
| | ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN |
| | BE DONE. |
| | PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE |
| | INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE |
| | INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE. |
| | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. ( |
| | TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS |
| | WHICH COULD NOT BE LOCATED ON PLANS. |
| | ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR |
| | MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE, |
| | HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED. |
| | |
| | 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK AS APPLIED WILL NEED TO BE REVISED BASED ON THE |
| | COMMENT ABOVE (NOTE #4). |
| | PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO |
| | INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT |
| | ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED. |
| | |
| | 6) NOTE:PLEASE SEE PANEL SCHEDULE SHOWS A 60AMP |
| | BREAKER ON #8 CONDUCTORS FOR INSTA-HOT, THESE |
| | CONDUCTORS ARE NOT RATED PER 110.14, 240.4, 310.16 |
| | |
| | 7) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD |
| | CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD. |
| | 5KW OR 8KW? |
| | PLEASE SEE220AND COORDINATE. |
| | FBC 106.1.2S |
| | |
| | 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS AS THE |
| | LOADS FOR INSTA-HOT HAVE NOT BEEN FIGURED INTO THE |
| | CALCULATIONS AS SHOWN.215.5, 215.3, 220, FBC |
| | 106.3.5.1.2 |
| | PLEASE ALSO SEE MISSING LOADS FOR SHOW WINDOWS PER THE |
| | NEXT COMMENT #9. 220.44/220.14 |
| | PLEASE ALSO SEE COMMENT FOR MISSING SIGN CIRCUIT AND |
| | LOADS NOT SHOWN. |
| | |
| | 9) NOTE: PLEASE SEE MISSING SHOW/DISPLAY WINDOW |
| | RECEPTACLES WHICH WILL BE REQUIRED PER 210.62 |
| | |
| | 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT EITHER NEW OR |
| | EXISTING PER 600.5 |
| | |
| | 11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE |
| | SEE THERE ARE FIXTURES AND J-BOXES WITH NO CIRCUITS, NO |
| | CONTROLS FOR LIGHTING (SEE NOTE#4) AND RECEPTACLES WITH |
| | NOT CIRCUITS. |
| | PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS. PLEASE |
| | SEE 408.4. |
| | PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO |
| | ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. THE |
| | USE OF *LIGHTING OR RECEPTACLES* IS NOT ACCEPTABLE PER |
| | CODE. |
| | PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM |
| | THE NEC 408.4. |
| | |
| | *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL |
| | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL |
| | BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON |
| | THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A |
| | PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A |
| | SWITCHBOARD.* |
| | |
| | PLEASE ALSO SEE THE NEC 2005 HANDBOOK WHICH CONTAINS A |
| | MORE EXTENSIVE COMMENTARY FOR THIS SAME SECTION. |
| | |
| | 12) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON |
| | PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION |
| | NEEDS TO BE UPDATE ON PERMIT APPLICATION. |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE |
| | BEING SHOWN ON THE SAME PAGE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-06-10 08:28:16 | 2007-06-10 08:28:16 |
| | REVIEW IN PROGRESS |
| 2007-06-09 20:32:15 | 2007-06-09 20:32:15 |
| | REVIEW TO CONTINUE ON 6/10 |
| | NOTES TO FOLLOW. |