Plan Review Notes
Plan Review Notes For Permit 07051114
Permit Number 07051114
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-10 08:55:32** UNSAT **
  
  
 ** PLEASE KNOW AS THERE AREITEMS ON PLANS WHICH WERE
 NOT SUBMITTED IN THE DESIGN FOR REVIEW, A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
 PLEASE KNOW THERE MAY BE NEW COMMENTS ON THE
 RE-SUBMITTAL OF PLANS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON
 ARCHITECTURAL/ELECTRICAL PLANS.
  
 2) NOTE: PLEASE SEE FS 481.229 AS A DRAFTING FIRM MAY
 NOT PRODUCE DOCUMENTS FOR THIS SCOPE OF WORK. THE
 ENGINEER AS STATED ON PLANS IS NOTED AS CIVIL AND
 STRUCTURAL, PLEASE SEE FS 471.025 FOR SCOPE OF WORK
 PERMITTED UNDER SPECIFIC LICENSE AND SCOPE OF
 KNOWLEDGE.
 PLEASE CONTACT THE STATE BOARD OF ENGINEERS FOR FURTHER
 QUESTIONS FOR THE SCOPE OF WORK UNDER ENGINEER. PLEASE
 CONTACT THE STATE BOARD OF ARCHITECTS LEGAL COUNSEL FOR
 ANY FURTHER QUESTIONS.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER AS SHOWN ON
 PLANS DOES NOT CORRELATE WITH THE ACTUAL SERVICE AT
 LOCATION OF JOBSITE. PLEASE SHOW SERVICE AT LOCATION OF
 THIS BUILDING.
 FBC 106.1.2, 106.3.5.1.2
 NEC 215.5
  
 4) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. THE ADOPTION OF THE 2004 FBC WAS OCT.1ST,
 2005 WHICH REQUIRED LIGHTING CONTROLS.
 A)PLEASE SEE PLANS WERE SUBMITTED WITH NO COMPLIANCE
 WITH 2004 FBC FOR CHAPTER 13 COMPLIANCE FOR AUTOMATED
 LIGHTING CONTROLS. AS NO SYSTEM, DEVICES OR CONTROLS OF
 ANY KIND IS SHOWN ON PLANS NO REVIEW ON MANY ITEMS CAN
 BE DONE.
 PLEASE INDICATE SYSTEM(S) OR TYPE OF CONTROLS. PLEASE
 INDICATE SCHEDULING.(IF A SYSTEM IS INSTALLED) PLEASE
 INDICATE ALL DEVICE LOCATIONS AS REQUIRED PER CODE.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES. (
 TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 B) PLEASE SEE 13-415.2 FOR THE PERFORMANCE CALCULATIONS
 WHICH COULD NOT BE LOCATED ON PLANS.
 ALL FIXTURES NEED TO BE SPECIFIED AT THIS TIME FOR
 MINIMUM DESIGN, THESE MAY BE REVISED AT A LATER DATE,
 HOWEVER A REVISION WILL BE REQUIRED TO BE SUBMITTED.
  
 5) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK AS APPLIED WILL NEED TO BE REVISED BASED ON THE
 COMMENT ABOVE (NOTE #4).
 PLEASE SEE FBC 108.3 WHICH REQUIRES THE VALUE TO
 INCLUDE ALL LABOR, MATERIALS, DESIGN COST, EQUIPMENT
 ETC, EVEN IF ANY OR PART IS OWNER SUPPLIED.
  
 6) NOTE:PLEASE SEE PANEL SCHEDULE SHOWS A 60AMP
 BREAKER ON #8 CONDUCTORS FOR INSTA-HOT, THESE
 CONDUCTORS ARE NOT RATED PER 110.14, 240.4, 310.16
  
 7) NOTE: PLEASE SEE PANEL SCHEDULE AND LOAD
 CALCULATIONS DO NOT CORRELATE FOR THE AHU HEAT LOAD.
 5KW OR 8KW?
 PLEASE SEE220AND COORDINATE.
 FBC 106.1.2S
  
 8) NOTE: PLEASE SUBMIT REVISED LOAD CALCULATIONS AS THE
 LOADS FOR INSTA-HOT HAVE NOT BEEN FIGURED INTO THE
 CALCULATIONS AS SHOWN.215.5, 215.3, 220, FBC
 106.3.5.1.2
 PLEASE ALSO SEE MISSING LOADS FOR SHOW WINDOWS PER THE
 NEXT COMMENT #9. 220.44/220.14
 PLEASE ALSO SEE COMMENT FOR MISSING SIGN CIRCUIT AND
 LOADS NOT SHOWN.
  
 9) NOTE: PLEASE SEE MISSING SHOW/DISPLAY WINDOW
 RECEPTACLES WHICH WILL BE REQUIRED PER 210.62
  
 10) NOTE: PLEASE SEE MISSING SIGN CIRCUIT EITHER NEW OR
 EXISTING PER 600.5
  
 11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE SUBMITTED PANEL SCHEDULES. PLEASE
 SEE THERE ARE FIXTURES AND J-BOXES WITH NO CIRCUITS, NO
 CONTROLS FOR LIGHTING (SEE NOTE#4) AND RECEPTACLES WITH
 NOT CIRCUITS.
 PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS. PLEASE
 SEE 408.4.
 PLEASE SEE THE PANEL SCHEDULES NEED TO BE SPECIFIC TO
 ALL ROOMS, AREAS AND CIRCUITING IN WHICH THEY FEED. THE
 USE OF *LIGHTING OR RECEPTACLES* IS NOT ACCEPTABLE PER
 CODE.
 PLEASE SEE THE FOLLOWING TEXT IS TAKEN DIRECTLY FROM
 THE NEC 408.4.
  
 *EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. THE IDENTIFICATION SHALL
 BE INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON
 THE FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANEL-BOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD.*
  
 PLEASE ALSO SEE THE NEC 2005 HANDBOOK WHICH CONTAINS A
 MORE EXTENSIVE COMMENTARY FOR THIS SAME SECTION.
  
 12) NOTE: PLEASE SEE THE OWNER INFORMATION AS STATED ON
 PERMIT APPLICATION IS NOT CORRECT AND THIS INFORMATION
 NEEDS TO BE UPDATE ON PERMIT APPLICATION.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT THE SAME SHEETS AS ALL TRADES ARE
 BEING SHOWN ON THE SAME PAGE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-10 08:28:162007-06-10 08:28:16
 REVIEW IN PROGRESS
2007-06-09 20:32:152007-06-09 20:32:15
 REVIEW TO CONTINUE ON 6/10
 NOTES TO FOLLOW.