Text |
| 2007-06-21 00:47:57 | *****DENIED***** |
| | |
| | |
| | 1.THE 2003 EDITION OF NFPA 101, THE LIFE SAFETY CODE, |
| | SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 4.PLEASE INDICATE IF THE BUILDING(S) OR PORTION OF |
| | THE BUILDING(S) IS/ARE TO BE OCUPIED DURINGTHE SCOPE |
| | OF WORK.IF SO, THEY SHALL BE PERMITTEDTO BE |
| | OCCUPIED ONLY WHERE THE REQUIRED MEANS OF EGRESS AND |
| | REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND |
| | CONTINUOUSLY MAINTAINED. |
| | |
| | 5.INDICATE IF THE BUILDING(S) SPRINKLERED.IF THE |
| | SCOPE OF WORK CAUSES MODIFICATION TO THE SPRINKLER |
| | SYSTEM, SEPARATE PLANS AND PERMIT SHALLL BE REQUIRED. |
| | |
| | 6.SEPARATE PLANS AND PERMIT SHALL BE REQUIRED FOR THE |
| | FIRE ALARM REMODEL. |
| | |
| | 7.IN THE ELECTRICAL FIXTURE QUANTITY SCHEDULE ON |
| | DRAWING A-2, IT LISTS THAT NO NEW SMOKE DETECTORS WILL |
| | BE ADDED.HOWEVER A NEW SMOKE DETECTOR (NSD) IS SHOWN |
| | ON THE PROPOSED FIRST FLOOR CEILING PLAN. |
| | |
| | 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW |
| | WALLS TO BE ERECTED AS CLASS A,CLASS B , OR CLASS C. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |