Plan Review Notes
Plan Review Notes For Permit 07051094
Permit Number 07051094
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-06-21 00:47:57*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, THE LIFE SAFETY CODE,
 SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.PLEASE INDICATE IF THE BUILDING(S) OR PORTION OF
 THE BUILDING(S) IS/ARE TO BE OCUPIED DURINGTHE SCOPE
 OF WORK.IF SO, THEY SHALL BE PERMITTEDTO BE
 OCCUPIED ONLY WHERE THE REQUIRED MEANS OF EGRESS AND
 REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE AND
 CONTINUOUSLY MAINTAINED.
  
 5.INDICATE IF THE BUILDING(S) SPRINKLERED.IF THE
 SCOPE OF WORK CAUSES MODIFICATION TO THE SPRINKLER
 SYSTEM, SEPARATE PLANS AND PERMIT SHALLL BE REQUIRED.
  
 6.SEPARATE PLANS AND PERMIT SHALL BE REQUIRED FOR THE
 FIRE ALARM REMODEL.
  
 7.IN THE ELECTRICAL FIXTURE QUANTITY SCHEDULE ON
 DRAWING A-2, IT LISTS THAT NO NEW SMOKE DETECTORS WILL
 BE ADDED.HOWEVER A NEW SMOKE DETECTOR (NSD) IS SHOWN
 ON THE PROPOSED FIRST FLOOR CEILING PLAN.
  
 8.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALLS TO BE ERECTED AS CLASS A,CLASS B , OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722