Plan Review Notes
Plan Review Notes For Permit 07051094
Permit Number 07051094
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-10 09:18:47** UNSAT **
  
 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE
 CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS
 OF DECEMBER 8TH, 2006.
 PLEASE LIST THE FOLLOWING.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC) 2002 SHOWN.
 2003 NFPA-101
 2002 NFPA-72
  
 THIS IS REQUIRED AT A MINIMUM ON
 ARCHITECTURAL/ELECTRICAL PLANS.
  
 2) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORNS,
 STROBES OR COMBO DEVICES TO MEET ADA 11-4.28.1, 2 AND
 .3(4).
  
 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND
 CHAPTER 13. 13-101 AS IF THE SQ FT FOR BUILDING IS 5K
 SQ FT, THEN ONLY THE DEVICES/SWITCHES AS SHOWN ON PLANS
 WILL BE REQUIRED TO MEET AUTOMATED CONTROLS.
 PLEASE STATE THE DEVICE TYPE AND MAXIMUM ALLOWED
 TIMES.
 ( TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
  
  
 4) NOTE11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS
 AND CORRELATE WITH A SUBMITTED PANEL SCHEDULE. PLEASE
 SEE THERE ARE ROOMS AND AREAS WHERE FIXTURES DO NOT
 INDICATE CIRCUITS, NO CONTROLS FOR LIGHTING (SEE
 NOTE#3)
 PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS.
 PLEASE SEE 408.4.
 LS 101 7.8, 7.9
  
 5) NOTE: PLEASE LABEL NEW ROOM WHICH INDICATES THE
 ELECTRICAL PANEL AND TIME CLOCK. 110.26, 408.7 ETC
 THE DOOR WILL BE REQUIRED TO CONTAIN A SIGN FOR *NO
 STORAGE*ELECTRICAL ROOM* OR WORDS TO THAT AFFECT. THE
 FIRE MARSHAL HAS TYPICAL WORDING USED, PLEASE CALL TO
 OVER IF NEEDED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved