| Date |
Text |
| 2007-06-10 09:18:47 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE CODES ON PLANS NEED TO BE |
| | CORRECTED TO THE LATEST CODES ADOPTED BY THE STATE AS |
| | OF DECEMBER 8TH, 2006. |
| | PLEASE LIST THE FOLLOWING. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC) 2002 SHOWN. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | THIS IS REQUIRED AT A MINIMUM ON |
| | ARCHITECTURAL/ELECTRICAL PLANS. |
| | |
| | 2) NOTE: PLEASE INDICATE THE MINIMUM LEVELS FOR HORNS, |
| | STROBES OR COMBO DEVICES TO MEET ADA 11-4.28.1, 2 AND |
| | .3(4). |
| | |
| | 3) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS AND |
| | CHAPTER 13. 13-101 AS IF THE SQ FT FOR BUILDING IS 5K |
| | SQ FT, THEN ONLY THE DEVICES/SWITCHES AS SHOWN ON PLANS |
| | WILL BE REQUIRED TO MEET AUTOMATED CONTROLS. |
| | PLEASE STATE THE DEVICE TYPE AND MAXIMUM ALLOWED |
| | TIMES. |
| | ( TIMERS 4HRS MAX AND OS TYPE DEVICE 30 MINS MAX). |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | |
| | |
| | 4) NOTE11) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS |
| | AND CORRELATE WITH A SUBMITTED PANEL SCHEDULE. PLEASE |
| | SEE THERE ARE ROOMS AND AREAS WHERE FIXTURES DO NOT |
| | INDICATE CIRCUITS, NO CONTROLS FOR LIGHTING (SEE |
| | NOTE#3) |
| | PLEASE COMPLETE SW-LEGS FOR LIGHTING CONTROLS. |
| | PLEASE SEE 408.4. |
| | LS 101 7.8, 7.9 |
| | |
| | 5) NOTE: PLEASE LABEL NEW ROOM WHICH INDICATES THE |
| | ELECTRICAL PANEL AND TIME CLOCK. 110.26, 408.7 ETC |
| | THE DOOR WILL BE REQUIRED TO CONTAIN A SIGN FOR *NO |
| | STORAGE*ELECTRICAL ROOM* OR WORDS TO THAT AFFECT. THE |
| | FIRE MARSHAL HAS TYPICAL WORDING USED, PLEASE CALL TO |
| | OVER IF NEEDED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |