| 2007-06-16 12:53:26 | BUILDING PLAN REVIEW |
| | PERMIT: 07051094 |
| | ADD: 1901 S.FLAGLER DR |
| | CONT: PRETI CONSTRUCTION, INC |
| | TEL: (561)840-9949 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | |
| | 3)INDICATE THE ALTERATION-LEVEL PER 2004 FLORIDA |
| | EXISTING BUILDING CODE CH.3 |
| | |
| | 4)INDICATE THE SLOPE /LENGTH AND WIDTH OF THE RAMP. |
| | 11-4.8.2 SLOPE & RISE. THE LEAST |
| | POSSIBLE SLOPE SHALL BE USED FOR ANY |
| | RAMP. THE MAXIMUM SLOPE FOR A RAMP IN |
| | NEW CONSTRUCTION SHALL BE 1 TO 12. THE |
| | MAXIMUM RISE FOR RUN SHALL BE 30" (SEE |
| | FIGURE 16).11-4.8.3. CLEAR WIDTH. THE MINIMUM CLEAR |
| | WIDTH OF A RAMP SHALL BE 36". |
| | EXCEPTION: RAMPS THAT ARE PART OF A |
| | REQUIRED MEANS OF EGRESS SHALL NOT BE |
| | LESS THAN 44 INCHES WIDE. |
| | |
| | 5)11-4.5.1 GROUND AND FLOOR SURFACES ALONG ACCESSIBLE |
| | ROUTES AND IN ACCESSIBLE ROOMS AND SPACES INCLUDING |
| | FLOORS, WALKS, RAMPS, STAIRS, AND CURB RAMPS, SHALL BE |
| | STABLE, FIRM, SLIPRESISTANT, AND SHALL COMPLY WITH |
| | SECTION 11-4.5 . |
| | |
| | 6)THE HANDRAILS SHALL MEET THE REQUIREMENTS OF FBC. |
| | 11-4.8.5 |
| | |
| | 7)11-4.24.1 SINKS REQUIRED TO BE ACCESSIBLE BY |
| | SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.24 . SHOW |
| | CONPLIANCE. |
| | |
| | 8)106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. PROVIDE TWO COPIES OF THE |
| | PRODUCT APPROVALS FOR THE 8 INCH LINTEL. |
| | |
| | 9)ADDITIONAL STRUCTURAL INFORMATION IS REQUIRED FOR |
| | THE WALL SECTION WHERE THE SINGLE DOOR AND WALL WILL BE |
| | REMOVED. SHOW THE STRUCTURAL SUPPORT OF THE WALL. THE |
| | BUILDING OFFICIAL MAY REQUIRE DETAILS, COMPUTATIONS, |
| | STRESS DIAGRAMS, AND OTHER DATA NECESSARY TO DESCRIBE |
| | THE CONSTRUCTION OR INSTALLATION AND THE BASIS OF |
| | CALCULATIONS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |