| 2007-06-15 08:21:23 | *** DENIED *** |
| | 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT. |
| | |
| | 2) PLEASE BE AWARE. PER 2004 FBC, FUEL GAS - POWERED |
| | EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY |
| | INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AND NFPA 37. |
| | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| | ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) |
| | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS |
| | IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING |
| | COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED |
| | WHEN |
| | (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE |
| | RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS |
| | CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| | BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL |
| | NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| | INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT |
| | TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT |
| | BE DRAWN INTO THE VENTILATION INTAKES. |
| | |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED |
| | BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| | STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT |
| | TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS |
| | SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES |
| | TO THE ADJACENT |
| | PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS, |
| | DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND |
| | EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD |
| | INSPECTOR. |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |