| Plan Review Notes For Permit 07051085 |
| Permit Number |
07051085 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-08 16:40:52 | DENIED BY BUILDING | | | | | | 1) THE MAXIMUM DESIGN PRESSURE FOR THE FASTENING OPTION | | | SPECIFIED ON PAGE 28 OF THE NOA FOR THE GAF MODIFIED | | | ROOFING IS -52.5 PSF IS TOO LOW FOR THE PERIMETER AND | | | CORNER AREAS OF THE ROOF. SUBMIT RAS 117 CALCULATIONS | | | FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER | | | 7 OF THE NOA. THIS WAS REQUESTED IN ITEM NUMBER 4 OF | | | THE FIRST REVIEW. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|