| 2007-06-20 14:09:57 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR |
| | PLAN REVIEW PER FBC-2004 CHAPTER 1, SECTION 106.1. |
| | |
| | 2. SHEET A3 PLUMBING RISER: THE SUBMITTED SANITARY |
| | ISOMETRIC RISER DIAGRAM DOES NOT REFLECT THE FLOOR |
| | PLAN. PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELAVENT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. PLEASE REFERENCE THE FOLLOWING RED LINE |
| | CORRECTIONS ON THIS SHEET FOR THE RESUBMITTAL. |
| | A} THE UNDERGROUND FITTING FOR THE LAV IS BEING |
| | INDICATED IN THE WRONG PLACE. |
| | B} THE WASHING MACHINE BOX AND CLEANOUT ARE BEING |
| | INDICATED IN THE BEDROOM NOT IN THE LAUNDRY ROOM. |
| | |
| | 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS. |
| | NOTE: PLEASE REFERENCE THE THE RED LINE PIPE SIZING FOR |
| | THE RESUBMITTAL ON SHEET A3 AND THE FOLLOWING THAT IS |
| | REQUIRED FOR THE WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE WASHING MACHINE |
| | STANDPIPE ON THE RESUBMITTAL. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | THREE INCH (3"). PLEASE INDICATE THIS ON THE |
| | RESUBMITTAL. |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | LOCATED AT FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). |
| | PLEASE INDICATE THIS ON THE RESUBMITTAL. |
| | |
| | 4. SHEET A3 PLUMBING RISER IS INDICATING THE NEW |
| | PROPOSED PLUMBING TO "CONNECT TO EXIST. S.S." PLEASE |
| | CLEARLY INDICATE WHAT "S.S." IS ON THE RESUBMITTAL AND |
| | THAT PER FBC-2004, PLUMBING, SECTION 909.1, ONLY THE |
| | FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| | WET VENT. PLEASE CLEARLY INDICATE THIS ON THE |
| | RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |
| | |
| | |
| | |