Plan Review Notes
Plan Review Notes For Permit 07051056
Permit Number 07051056
Review Stop M
Sequence Number 1
Notes
Date Text
2007-06-01 11:31:51*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2. AND HAVE ENERGY CALCULATIONS SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 3) MECHANICAL PLAN EQUIPMENT SCHEDULE IS CALLING FOR A
 12 SEER A/C SYSTEM, THE MINIMUM SEER THAT MAY BE
 INSTALLED IS 13 SEER, PLEASE CHANGE A/C SYSTEM, SEE
 2004 FBC 13-607.1.ABC.3.2.1.
  
 4) PLEASE SHOW CFM'S OF BATHROOM EXHAUST FAN ON
 MECHANICAL PLAN.
  
 5) PLEASE SHOW THE SIZES OF ALL SUPPLY AIR GRILLS ON
 PLANS.
  
 6) PLEASE SHOW ON MECHANICAL PLAN THE RETURN AIR DUCTS,
 AND HOW AIR IS GETTING BACK TO THE AHU.
  
 7) PLEASE SUBMIT TWO COPY'S OF PLANS AND ALL OTHER
 PAPER WORK.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.