| 2007-06-15 13:17:54 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY |
| | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | 2} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR |
| | REVIEW PER 106.1 FBC AS AMENDED. |
| | |
| | 3} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | THE PANEL SHOWN OVER THE COUNTER IS IN VIOLATION OF |
| | 110.26. |
| | |
| | 4} INDICATE THE CONDUIT SIZE, WIRE SIZE NUMBER & TYPE, |
| | BETWEEN THE DISCONNECT AND PANEL ON THE RISER. ALSO SEE |
| | 250.122. |
| | |
| | 5} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 6} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED |
| | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A |
| | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. |
| | |
| | 7} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| | VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS." |
| | |
| | 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1) |
| | AND 210.52 (A) (2). SEE MASTER BEDROOM. |
| | |
| | 9} GFI'S ARE REQUIRED IN THE GARAGE PER 210.8(A)(2). |
| | |
| | 10} RECEPTACLES ARE REQUIRED AT THE FRONT AND REAR |
| | OUTSIDE, 210.52(E) AND 210.8(A)(3), GFI. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |