Plan Review Notes
Plan Review Notes For Permit 07051056
Permit Number 07051056
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-04 10:00:44 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS(SEE STRUCTURAL NOTES)
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 639.00 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8)CORRECT ADDRESSON PERMIT AND DRAWINGS TO MATCH
 OFFICIAL RECORD FOR THAT PCN WHICH IS 714 - 45 ST
  
 9)PROVIDE AT MINIMUM 1 ACCESSIBLE BATHROOM PER
 R322.1.1 FBC 29" CLEAR WITH DOOR OPEN 90 DEGREES
  
 10)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 11)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR
 MIN BEARING
  
 12)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF
 FOUNDATION ON THE WALL SECTIONS PER R403.1.4 FBC RES.
  
 13)DRAWINGS STATE PGT WINDOWS IF YALE OGRON ARE TO BE
 USED REMOVE PGT FROM DRAWINGS, ALSO 3843 SH WINDOWS
 USED IN THE MASTER BEDROOM AND BEDROOM 1 DO NOT MEET
 EGRESS REQUIREMENTS
  
 14)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THATIS RELEVANT PER 9B-72.
 THESE SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES. ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
  
 15)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
  
 16)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 17)NO PRODUCT APPROVALS WERE SUBMITTED FOR EXTERIOR
 DOORS, LINTELS, MULLIONS FOR JOINED WINDOWS AND
 CONNECTORS AND STRAPS
  
 18)ENGINEERED TRUSS DRAWINGS ARE MISSING INDIVIDUAL
 TRUSS SHEETS WITH SIGNED AND SEALED COVER SHEET
  
 19)PROVIDE 2 COMPLETE SETS OF ALL DRAWINGS AND
 SUBMITTALS
  
 20)OWNER BUILDER EXEMPTION CANNOT BE CLAIMED FOR
 PROPERTY THAT IS RENTED OR LEASED. THIS OWNER HAS THREE
 PROPERTIES ONE AT 616 - 48TH ST THAT IS CONSIDERED MAIN
 RESIDENCE AND HAS HOMESTEAD EXEMPTION. PLEASE FILL OUT
 A CHANGE OF CONTRACTOR FORM AND HAVE A LICENSED
 CONTRACTOR PERFORM THE WORK.
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  