2007-06-13 12:08:31*****DENIED*****
  
  
 1.DUE TO THE TINT OF THE SUBMITTED PLAN SHEETS, THIS
 WRITER WAS UNABLE TO READ WORDING IN SOME OF THE
 DETAILS.
  
 2.AMEND GENERAL NOTE #1 TO REFLECT THAT NFPA 13 (2002
 EDITION) IS REFERENCED.
  
 3.SHOW THE LOCATION AND THE DETAIL OF THE FIRE
 DEPARTMENT CONNECTION.
  
 4.KNOX LOCKING CAPS SHALL BE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION PRIOR TO THE FINAL SPRINKLER
 INSPECTION.FOR AN APPLICATION, CONTACT WEST PALM
 BEACH FIRE PREVENTION AT 561-804-4724.
  
  