Plan Review Notes
Plan Review Notes For Permit 07051000
Permit Number 07051000
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-01 11:19:20 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI, PLEASE
 LOCATE SAME ON PLANS.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 NOTE:R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS
 REQUIRED IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE
 TEXT.
  
 713.13NOTICE OF COMMENCEMENT.--
  
 (1)(A)EXCEPT FOR AN IMPROVEMENT THAT IS EXEMPT
 PURSUANT TO S. 713.02(5), AN OWNER OR THE OWNER'S
 AUTHORIZED AGENT BEFORE ACTUALLY COMMENCING TO IMPROVE
 ANY REAL PROPERTY, OR RECOMMENCING COMPLETION OF ANY
 IMPROVEMENT AFTER DEFAULT OR ABANDONMENT, WHETHER OR
 NOT A PROJECT HAS A PAYMENT BOND COMPLYING WITH S.
 713.23, SHALL RECORD A NOTICE OF COMMENCEMENT IN THE
 CLERK'S OFFICE AND FORTHWITH POST EITHER A CERTIFIED
 COPY THEREOF OR A NOTARIZED STATEMENT THAT THE NOTICE
 OF COMMENCEMENT HAS BEEN FILED FOR RECORDING ALONG WITH
 A COPY THEREOF. THE NOTICE OF COMMENCEMENT SHALL
 CONTAIN THE FOLLOWING INFORMATION:
  
 THE OWNER/BUILDER DISCLOSURE STATEMENT MUST BE SIGNED
 BY SAME, NOT AN AGENT. SEE FORM. PLEASE COME IN WHEN
 RESUBMITTING AND SIGN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  