| 2007-09-07 18:52:12 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE:THIS IS THE SAME COMMENT AS PREVIOUS REVIEW. |
| | THE RESPONSE MENTIONS THIS WAS UPDATED ON SHEET A-0.1 |
| | HOWEVER IT WAS ASKED FOR THE RELEVANT CODES TO BE |
| | PLACED ON ELECTRICAL SHEETS HOWEVER THIS WAS NOT DONE. |
| | PLANS ONLY STATE THE *LATEST ADOPTED CODES*. |
| | AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND |
| | CORRECTION PLEASE INCLUDE ON ELECTRICAL PLANS. |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE BE SURE TO STATE ALL THE RELEVANT CODES AS |
| | ADOPTED BY THE STATE OF FLORIDA AS OF DECEMBER 8TH, |
| | 2006. |
| | PLEASE SEE THE FOLLOWING AT A MINIMUM MUST BE STATED. |
| | SOME CODES STATED NEVER EXISTED.(2003 NEC) |
| | |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 (DONE ON COVER ALTHOUGH REQUIRED ON |
| | ELECTRICAL SHEETS) |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE BE AWARE OF ANY POSSIBLE CODES FROM OTHER |
| | TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR THE ARCHITECTURAL FIRM ON E-SHEETS. AS THESE SHEET |
| | ARE BEING CORRECTED FOR OTHER COMMENTS, PLEASE SEE THE |
| | PRINTED FIRM CERTIFICATE OF AUTHORIZATION NUMBER IS THE |
| | ONLY ITEM THAT IS MISSING. 61G1-16.004 FOR ARCHITECT |
| | FIRM. |
| | |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT THIS COMMENT IS MADE BY ANY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| | FBC HAS NOT BEEN MET. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED ONCE |
| | AGAIN DO NOT CORRELATE WITH PLANS OR THE FIXTURE LEGEND |
| | AS SUBMITTED. PLEASE SEE THERE ARE IN FACT SEVERAL HAND |
| | PRINTED ITEMS ON THE INPUT DATA REPORT WHICH MUST BE |
| | PLACED INTO THE IDR WHEN RUNNING REPORT. |
| | PLEASE CORRELATE. |
| | PLEASE SEE THE LIGHTING FIXTURE TYPES DO NOT MATCH. |
| | PLEASE SEE THE WATTAGE ON FIXTURES DOES NOT MATCH. |
| | PLEASE SEE THE NUMBER OF EACH FIXTURE ALSO DOES MATCH. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR REQUIRED TRACK |
| | LIGHTING CALCULATIONS AND FIGURES. |
| | ** PLEASE SEE THE FBC 13-415.1.B.1.1, 13-415.2 AND |
| | TABLES FOR METHOD *B*. |
| | PLEASE SEE THE REQUIRED LIGHTING CONTROLS ARE NOT |
| | SHOWN ON PLANS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2. |
| | PLEASE INDICATE TIME FOR SCHEDULING IF A LIGHTING |
| | CONTROL SYSTEM IS INSTALLED ALONG WITH ALL OVER RIDE |
| | DEVICE TIMES. |
| | PLEASE PROVIDE MORE INFORMATION/DETAIL FOR THE TIME |
| | CLOCK BEING NOTED. |
| | AT THIS TIME. |
| | |
| | 4) NOTE: PLEASE SEE NOTE #10 ON SHEET E-2.0 MENTIONS |
| | THE FIRE ALARM PANEL IS TO BE CIRCUITED TO PANEL *A* |
| | 41, YET THIS SPACE IS BEING SHOWN AS SPARE? |
| | PLEASE COORDINATE. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | NEC 408.4. |
| | |
| | 5) NOTE: PLEASE SEE 220.53 FOR MINIMUM LOADS TO BE |
| | FIGURED FOR SHOW WINDOW RECEPTACLES. PLEASE ADJUST |
| | SERVICE CALCULATIONS. |
| | RESPONSE MENTIONS TO REFER TO REVISED CALCULATIONS |
| | HOWEVER HOW THE SHOW WINDOW LOAD WAS DERIVED OR SHOWN |
| | IN THESE CALCULATIONS IS NOT CLEAR. |
| | |
| | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | TWO SETS OF ELECTRICAL PLANS AND ENERGY CALCULATIONS |
| | ARE BEING RETAINED BY THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** AS STATED IN THE PREVIOUS REVIEW,: |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |