| 2007-09-11 08:22:47 | BUILDING PLAN REVIEW |
| | PERMIT: 07050998 |
| | ADD: 550 S.ROSEMARY AVE |
| | CONT: RCC ASSOCIATES, INC. |
| | TEL: (954)429-3700 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)F.A.C. 61G15-23.002ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET, IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. SEE 61G1-16.004 / |
| | F.S. 471.023 / 481.219. |
| | **THE NEW ARCHITECTURAL SHEETS ARE MISSING THE SEAL OF |
| | THE ARCHITECT AND THE DATE WHICH THEY WERE SEALED. ONE |
| | SET OF NEW PLANS IS MISSING THE ELECTRICAL SHEETS. OUR |
| | OFFICE SHALL RETAIN ON SET AS PROOF THE PLANS WERE NOT |
| | SEALED. |
| | |
| | 3)INDICATE HOW WALL DETAIL # 2 ON SHEET A-4.0 WILL BE |
| | ATTATCH TO THE EXISTING STRUCTURE? |
| | |
| | 4)OK |
| | |
| | 5)OK |
| | |
| | 6)OK |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | [email protected]. |